Product Data Sheet / Brochure

©2013EatonCorporation
All Rights Reserved
9PXBrochureA4revD
November2013
Eaton is a registered trademark
ofEatonCorporation.
All other trademarks are property
of their respective owners.www.eaton.eu/9PX
Due to continuing product improvement programmes, specifications are subject to change without notice.
Accessories Rack kit: 9RK, Transformer (Single Phase): TFMR11Ki, Battery Integration System: BINTSYS
Eaton 9PX UPS Technical Spec i fi ca tions
Technical Specifications 5kVA 1:1 6kVA 1:1 6kVA 3:1 8kVA 1:1 or 3:1 11kVA 1:1 or 3:1
Rating (kVA/kW) 5kVA/4.5kW 6kVA/5.4kW 6kVA/5.4kW 8kVA/7.2kW 11kVA/10kW
Electrical Characteristics
Technology On-line double conversion with Power Factor Correction (PFC) system
Input voltage 200/208/220/230/240V 1:1 200/208/220/230/240V/250V 1:1, 380/400/415 3:1
Input voltage range 176-276V without derating (up to 100-276V with derating) 1:1, 305V-480V without derating (up to 175V-480V with derating) 3:1
Output voltage/THDU 200/208/220/230/240V +/– 1%; THDU <2%
Input frequency range/THDI 40-70Hz, 50/60Hz autoselection, frequency converter as standard, THDI < 5%
Efficiency Up to 94% in Online mode, 98% in Hi-Efficiency mode Up to 95% in Online mode, 98% in Hi-Efficiency mode
Short circuit current 90A 90A 90A 120A 150A
Overload capacity 102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 500ms 102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 900ms
Connections
Input Terminal block (up to 10 mm
2
) Terminal block (up to 16mm
2
)
Outputs
Terminal block +
2 controlled groups of 4 IEC C13 (10A) + 2 IEC C19 (16A)
Terminal block
Outputs with HotSwap Maintenance Bypass Terminal block + 3 IEC C13 (10A) + 2 IEC C19 (16A) Terminal block + 4 IEC C19 (16A)
Batteries
Typical backup times at 50 and 70% load*
9PX 13/10 min 11/8 min 30/20min 20/15 min 13/9min
9PX + 1 EBM 60/40 min 48/34 min 70/45min 48/32 min 32/21 min
9PX + 4 EBM 220/150 min 170/120 min 210/140 min 140/100 min 100/70 min
Battery management ABM
®
and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units.
Communication
Communication ports
1 USB port, 1 RS232 serial por t (USB and RS232 por ts cannot be used simultaneously), 4 dr y contacts (DB9), 1 mini terminal block for remote On/Off and 1 for remote power Off,
1 DB15 for parallel operation.
Communication slot 1 slot for Network-MS card (included in Netpack versions), ModBus-MS or Relay-MS cards.
Operating conditions, standards and approvals
Operating temperature 0 to 40°C continuous
Noise level <45dB <45dB <48db <48db <50db
Safety IEC/EN 62040-1, UL 1778 (1:1 version)
EMC, performance IEC/EN 62040 -2, FCC Class A (1:1 version), IEC/EN 62040-3 (Performance)
Approvals CE, CB report (TUV), UL (1:1 version)
Dimensions H x W x D/Weight
UPS dimensions 440(19’’)*130(3U)*685mm 440(19’’)*130(3U)*685mm 440(19’’)*260(3U+3U)*700mm 440(19’’)*260(3U+3U)*700mm 440(19’’)*260(3U+3U)*700mm
UPS weight 48kg 48kg 88kg 84kg (1:1), 88kg (3:1) 86kg (1:1), 88kg (3:1)
EBM dimensions 440(19’’)*130(3U)*645mm 440(19’’)*130(3U)*645mm 440(19’’)*130(3U)*680mm 440(19’’)*130(3U)*680mm 440(19’’)*130(3U)*680mm
EBM weight 68kg 68kg 65kg 65kg 65kg
Power module dimensions - - 440(19’’)*130(3U)*700mm 440(19’’)*130(3U)*700mm 440(19’’)*130(3U)*700mm
Power module weight - - 23kg 19kg (1:1), 23kg (3:1) 21kg (1:1), 23kg (3:1)
Customer Service and Support
Warranty 2 years warranty
* Runtimes are shown at 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc
1 RemoteOff/OnandRemote
Power Off connectors
2 Slot for Network-MS,
ModBus-MS or Relay-MS cards
3 Parallel operation
port(DB15)
4 External battery module
(EBM) connector with
automatic detection (RJ11)
Parts Numbers 9PX 5kVA 1:1 9PX 6kVA 1:1 9PX 8kVA 1:1 9PX 11kVA 1:1 9PX 6kVA 3:1 9PX 8kVA 3:1 9PX 11kVA 3:1
UPS with HotSwap Maintenance Bypass 9PX5KiBP 9PX6KiBP 9PX8KiBP 9PX11KiBP 9PX6KiBP31 9PX8KiBP31 9PX11KiBP31
UPS with Network Card and Rack Kit 9PX5KiRTN 9PX6KiRTN
UPS with HotSwap MBP, Network Card
and Rack Kits
9PX8KiRTNBP 9PX11KiRTNBP 9PX6KiRTNBP31 9PX8KiRTNBP31 9PX11KiRTNBP31
EBM 9PXEBM180 9PXEBM180 9PXEBM240 9PXEBM240 9PXEBM240 9PXEBM240 9PXEBM240
Power Module 9PX8KiPM 9PX11KiPM 9PX6KiPM31 9PX8KiPM31 9PX11KiPM31
HotSwap Maintenance Bypass MBP6Ki MBP6Ki MBP11Ki MBP11Ki MBP11Ki31 MBP11Ki31 MBP11Ki31
9PX ModularEasy (paralleling kit)
9PXMEZ6Ki 9PXMEZ6Ki 9PXMEZ11Ki 9PXMEZ11Ki
Supercharger with Rack Kit SC240RT SC240RT SC240RT SC240RT SC240RT
1.8m Battery Connection Cable EBMCBL180 EBMCBL180 EBMCBL240 EBMCBL240 EBMCBL240 EBMCBL240 EBMCBL240
5 8IEC10Asockets(2groups
of 4 manageable sockets)
with cable retention system
6 2IEC16Asocketswithcable
retention system
7 DB9withoutputcontacts
8 USB and serial ports
9 Input/Ouputconnection
Eaton 9PX 6kVA 1:1
9PX Parallel*
9PX 10kVA 1:1
(5kVA redundant)
9PX 12kVA 1:1
(6kVA redundant)
9PX 16kVA 1:1
(8kVA redundant)
9PX 22kVA 1:1
(11kVA redundant)
9PXM10KiRTN 9PXM12KiRTN 9PXM16KiRTN 9PXM22KiRTN
*9PX Parallel system includes 2 x 9PX, ModularEasy (Parallel kit), rail kits and network cards