2. Presentation
2.5 LCD description
After 5 minutes of inactivity, the LCD displays the screen saver.
The LCD backlight automatically dims after 10 minutes of inactivity. Press any button to restore the screen.
Operation status
Load/equipment status
Online mode
100%
19min
1EBM
100%
2.7kW
3.0kVA
Efficiency: 94%
Battery status
Efficiency and load group information
The following table describes the status information provided by the UPS
Note: If other indicator appears, see troubleshooting on page 35 for additional information.
Operation status Cause Description
Standby mode
The UPS is Off, waiting form start-
up command from user.
Equipment is not powered until
button is pressed.
Online mode
The UPS is operating normally. The UPS is powering and protecting
the equipment.
Battery mode
1 beep every 10 seconds
A utility failure has occured and
the UPS is on Battery mode.
The UPS is powering the equipment
with the battery power.
Prepare your equipment for shut-
down.
End of backup time
1 beep every 3 seconds
The UPS is on Battery mode and
the battery is running low.
This warning is approximate, and
the actual time to shutdown may
vary significantly.
High Efficiency mode
The UPS is operating on High
Efficiency mode.
The UPS is powering and protecting
the equipment.
Bypass mode
An overload or a fault has occurred,
or a command has been received,
and the UPS is on Bypass mode.
Equipment is powered but not
protected by the UPS.