Technical Data TD158002EN
Effective September 2013
AEGIS Series line lters
and surge protectors
Product selection
Table 5. Catalog Numbering System
a
Only available for 10A CF version.
AG
Product
Family/OEM
AG
Protection/Filtering Voltage Amperage Options
PH = Premium protection
with hybrid filtering
120 = 120 Vac
240 = 240 Vac
03 = 3A
05 = 5A
10 = 10A
15 = 15A
20 = 20A
PV = Premium protection
with filtering
120 = 120 Vac
240 = 240 Vac
01 = 1A
03 = 3A
05 = 5A
CF = Critical protection
with filtering
120 = 120 Vac
240 = 240 Vac
024 = 24 Vdc
048 = 48 Vdc
10 = 10A
30 = 30A
60 = 60A
DIN = DIN mount
a
CP = Compact
b
RJ = Telcom protection and
Form C status contacts
c
CN = Critical protection
without filtering
120 = 120 Vac
240 = 240 Vac
024 = 24 Vdc
048 = 48 Vdc
30 = 30A
b
Only available for 10A, 120V CF version.
c
Only available for 30A and 60A CF version.
Table 6. Let-Through Voltages Based on IEEE Std. C62.62-2010 Testing Waveforms
a
Test Impulse
AEGIS Series
xxPH120xx xxPV120xx xxCF12010 xxCF12010-DIN xxCF12010-CP xxCF12030xxx xxCF12060xxx xxCN12030
IEEE Category A
100 kHz ring wave
6000V, 200A
25V 30V 150V 300V 300V 150V 90V 400V
IEEE Category B
100 kHz ring wave
6000V, 500A
35V 40V 330V 400V 400V 330V 230V 500V
IEEE Category B
combination wave
6000V, 3000A
(UL 1449-3 VPR)
360V 370V 470V 480V 460V 460V 450V 460V
a
All tests conducted on 120 Vac units.
Technical support information
If you have any questions or need additional information, please
contact the Eaton Technical Resource Center at 800-809-2772,
option 4, option 2, or go to www.eaton.com/aegis. You may also
submit inquiries via email to spd@eaton.com