Datasheet

04/18/2017 185605 - HPL-ED2017 V31.0 EN 2 / 3
Tightening torque Threaded ring Nm 2
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Degree of Protection IP66, IP67, IP69K (front)
IP65 (on rear)
Mounting position As required
Mechanical shock resistance, shock duration 11 ms g > 30
Contacts
Rated impulse withstand voltage U
imp
V AC 4000
Rated insulation voltage U
i
V 250
Overvoltage category/pollution degree III/3
Control circuit reliability
At 17 V DC/7 mA H
F
N/O contact: statistically determined 1 failure per 17 × 106 operations
N/C contact: statistically determined 1 failure per 0.9 × 10
6
Operations
Max. short-circuit protective device
Fuse gG/gL A 4
Rated conditional short-circuit current Iq kA 1
Switching�capacity
Rated operational current I
e
A
AC-15
24 V I
e
A 4
DC-13
24 V I
e
A 3
Cable characteristics
Design Cable end open
Cable Length m 1
Material characteristic PUR
Diameter mm 4.7
Design�verification�as�per�IEC/EN�61439
Technical data for design verification
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 70
Technical�data�ETIM�6.0
Low-voltage industrial components (EG000017) / Push button, complete (EC001028)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Command and alarm device / Push-button actuator, complete unit (ecl@ss8.1-27-37-12-28
[AKF046011])
Number of command positions 1
Colour button Without button plate
Construction type lens Round
Hole diameter mm 22
Width opening mm 0
Height meter opening mm 0
Degree of protection (IP) -
Type of button Flat
Suitable for illumination No
Switching function latching No
Spring-return Yes
Supply voltage lamp V 0
Number of contacts as normally open contact 1
Number of contacts as normally closed contact 1
Number of contacts as change-over contact 0
Type of electric connection -
With front ring Yes
Material front ring Plastic