Installation Manual

Ethernet module for use with C440, XTOE, ZEB,
S611 and as Stand-alone I/O
(Modbus TCP & EtherNet/IP)
Effective February 2012
Supersedes February 2012
Instruction Leafl et IL04209009E
Installation
The Ethernet module is designed to be used in
industrial applications and installed in accordance
with this document. The device is intended for use
in clean, dry environments.
Mount the module
The device has both #10 screw mounting feet and
a 35mm din rail spring mount feature.
To mount the adapter to a din rail place the top of
the device on the rail first then apply gentle down-
ward force while pushing the device flat against
the din rail.
Ethernet Port Connections
Connect the Ethernet cable to one of the Ethernet
ports. This adapter has an internal embedded
switch which provides two Ethernet ports. The two
ports provide the ability to create a linear or ring
configuration. In the star configuration either port
can be used.
This adapter supports Modbus TCP, EtherNet/IP
and HTTP.
Set the IP Address
The IP address is selected using the DIP switches.
See table one for DIP switch behavior.
Table 1. DIP Switch Settings
DIP switch
setting
Behavior
0 Use the static IP address of 192.168.1.254
1 to 253
Combine the upper three octets stored in
NVMemory with the DIP switch setting.
Example: If the static IP address programmed
from the network is100.100.100.0 and the DIP
switch is set to 5, the  nal IP address will be
100.100.100.5.
254
Use the full IP address stored in NVMemory.
The default NVMemory value is
192.168.1.254.
255
DHCP is used to de ne the IP address.
(Default)
Web Page Access
To configure or monitor the device through a web
browser, type the devices IP address into the web
browser address bar.
Standalone IO
Vendor ID 0x44 (68d)
Device Type 0x07 (7d) IO
Product Code 0x112A - 24Vdc IO
0x112B - 120Vac IO
C440 Solid State Overload
Vendor ID 0x44 (68d)
Device Type 0x03 (3d) Overload
Product Code 0x1130 - 24Vdc IO
0x1131 - 120Vac IO
S611 Softstarter
Vendor ID 0x44 (68d)
Device Type 0x17 (23d) Softstarter
Product Code 0x1133 - 24Vdc IO
0x1134 - 120Vac IO

Summary of content (4 pages)