Installation Manual

2
Instruction Lea et IL04209009E
February 2012
Ethernet module for use with C440, XTOE, ZEB,
S611 and as Stand-alone I/O
(Modbus TCP & EtherNet/IP)
EATON CORPORATION www.eaton.com
Default EtherNet/IP Assemblies
Table 2. EtherNet/IP - C440 Default Assemblies
Default Input
Assembly 0x78
(120d)
Word Data
0 Device status
1 Latched Fault Bits
2 RMS Current Avg
3 Thermal Mem%
Default Output
Assembly 0x69
(105d)
Byte Data
Control Byte
Bit Bit Definition
0 Output1
1 Output2
2 Fault Reset
3 Reserved
4 Reserved
5 Remote Trip
6-7 Reserved
*See Manual for full CIP Object Model.
Table 3. EtherNet/IP - S611 Default Assembly
Default Input
Assembly 0x79
(121d)
Word Data
0 Device Status
1 RMS Current Avg
2 RMS Voltage Avg
3 Overload Thermal
Pile
Default Output
Assembly 0x6A
(106d)
Byte Data
0 Control Byte
Bit Bit Definition
0 Run 1
1 Permissive
2 Fault Reset
3-5 Reserved
6 Out 1
7 Out 2
Modbus Register Summary
Table 4. Modbus Registers - Adapter IO
Modbus
Register R/W Description
1 R Adapter Inputs
101 R/W Adapter Relay Outputs
** See Manual for full Modbus register map.
Table 5. Modbus Registers - C440
Modbus
Register R/W Description
300 R Motor State:
0 = Stopped
1 = Running
2 = Tripped
301 R Phase A RMS Current
302 R Phase B RMS Current
303 R Phase C RMS Current
304 R Average RMS Current
305 R Thermal Memory Percentage
332 R/W
Command Register:
Bit 0 = 1 -> Trip
Bit 1 = 1 -> Reset
** See Manual for full Modbus register map.
Table 6. Modbus Registers - S611
Modbus
Register
R/W Description
300 R Motor Control Status
301 R Current Scale Factor
302 R Phase A RMS Current
303 R Phase B RMS Current
304 R Phase C RMS Current
305 R Average RMS Current
306 R Phase A RMS Voltage (L1-L2)
307 R Phase A RMS Voltage (L2-L3)
308 R Phase A RMS Voltage (L3-L1)
309 R Average RMS Voltage
310 R Motor Power (KW)
314 R Motor Thermal Capacity %
400 R/W Motor Control
** See Manual for full Modbus register map.