Installation Manual
3
Instruction Lea et IL04209009E
February 2012
Ethernet module for use with C440, XTOE, ZEB,
S611 and as Stand-alone I/O
(Modbus TCP & EtherNet/IP)
EATON CORPORATION www.eaton.com
NO
NO
NO
C
NC
Q1
Q1
Q2
C
Q2
Pin 1
Pin 12
Example: Isolated 24Vdc Input
Source
- Connect isolated power source
between C and Inputs.
AC/DC
AC/DC
C C
24VDCISO
0V
24
-
+
I4
I3
I2
I1
I4
I3
I2
I1
RS485 Ethernet
1
2
4
8
16
32
64
128
On
24VDC
Power Supply
ON
OFF
+
-
D0D1
Figure 2. C441V 24 Vdc Input Speci cation - Isolated
RS485
AC/DC
AC/DC
NO
NO
NO
C
NC
Q1
Q1
Q2
C
Q2
Pin 1
Pin 12
Example: Non Isolated 24Vdc Input Source
- Connect C and 0V together.
- Use 24 to source inputs.
I4
I3
I2
I1
C
I4
I3
I2
I1
C
0V
24
-
+
Ethernet
1
2
4
8
16
32
64
128
On
24VDC
Power Supply
ON
OFF
+
-
D0D1
Figure 3. C441V 24 Vdc input Speci cation - Non-Isolating
Table 9. 24 Vdc Inputs
Specification Value
Number of inputs 4
Nominal voltage 24Vdc
Nominal current 5 mA
Type Current Sinking
Input type IEC 61131-2, type 1 digital
Table 7. EtherNet/IP - S611 Default Assembly
Default Input
Assembly 0x79
(121d)
Word Data
0 Device Status
1 RMS Current Avg
2 RMS Voltage Avg
3 Overload Thermal
Pile
Default Output
Assembly 0x6A
(106d)
Byte Data
0 Control Byte
Bit Bit Definition
0 Run 1
1 Permissive
2 Fault Reset
3-5 Reserved
6 Out 1
7 Out 2
*See Manual for full CIP Object Model.
Example 120VAC IO Module
- All inputs are isolated.
AC/DC
AC/DC
120VAC
C
NO
NO
NO
C
NC
I1
I2
I3
I4
C
Q1
Q1
Q2
C
Q2
Pin 1
Pin 12
0V
24
-
+
+
-
D0D1
RS485 Ethernet
1
2
4
8
16
32
64
128
On
24VDC
Power Supply
ON
OFF
I1
I2
I3
I4
Figure 1. C441U - 120 Vac Input Speci cation
T
able 8. 120 Vac Inputs
Specification Value
Number of inputs 4
Nominal voltage 120Vac
Nominal current 15 mA
Type 50/60 Hz
Input type IEC 61131-2, type 1 digital