Ethernet module for use with C440, XTOE, ZEB,
S611 and as Stand-alone I/O
(Modbus TCP & EtherNet/IP)
Certifications
Agency certifications UL® 508
cUL® (CSA® C22.2 No. 14)
CE (low voltage directive)
EtherNet/IP conformance tested
Table 10. Environmental Ratings of the Module
Description Rating
Transportation and
Storage
Temperature -40°C to 85°C (-40°F to 185°F)
Humidity 5-95% non condensing
Operating Temperature -20°C to 55°C (-4°F to 131°F)
Humidity 5-95% non condensing
Altitude Above 6600 ft (2000m)
Consult factory
Shock
IEC 60068-2-27
15G any direction for 11 ms
Vibration
IEC 60068-2-6
5-150 Hz, 3G, 0.42mm
peak-to-peak
Pollution
Degree
3
Table 11. Module Electrical Requirements
Description Requirement
Voltage range 18–30 Vdc
Current draw Approx. 50 mA
otes: N
For use with Eaton UL Listed Power Supply Catalog Nos. PSS55A,
PSS55B, PSS55C or PSS160E.
Any UL Listed isolated power supply with a maximum of 30 Vdc output
may be used, provided that a UL Listed or Recognized Fuse rated no
more than 3 A maximum be installed.
Reference
C441/Standalone I/O Manual MN04201001E
S611 Manual MN03902011E