Cut Sheet

Volume 1—Residential and Light Commercial CA08100002E—August 2015 www.eaton.com V1-T2-3
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2.1
Surge Protection
Surge Protection Devices and Lightning Arresters
Two-Stage Protection
Plug-On Surge Protection
Ty p e C H S A —For use on
single-phase 120/240 Vac
systems. The CHSA easily
plugs into a single-phase
Type CH loadcenter and
occupies two 3/4-inch
(19.1 mm) pole spaces,
similar to a two-pole Type
CH breaker. When installed
properly, it provides surge
protection for the entire
loadcenter. If internal
components are damaged,
the CHSA LED visual
indicators will signal the
need for a replacement.
This device is suitable for
service entry locations
when installed in
accordance with NEC
®
guidelines
Ty p e B R S U R G E —For
use on single-phase
120/240 Vac systems. This
easily plugs into a single-
phase Type BR loadcenter
and occupies two 1-inch
(25.4 mm) pole spaces
similar to a two-pole Type
BR breaker. When installed
properly, it provides surge
protection for the entire
loadcenter. If internal
components are damaged,
the BRSURGE LED visual
indicators will signal the
need for replacement.
This device is suitable
for service entry locations
when installed in
accordance with NEC
guidelines. This unit is
also classified by UL for
use in select GE, ITE/
Siemens and Crouse-Hinds
Panels (refer to Pub No.
5655B65H01 for additional
details)
1
CHSP installed at the service entrance panel.
2
SurgeTrap™ surge traps and strips located where sensitive electronics are plugged in.
Ty p e C H Q S A —For use
on single-phase, 120/240 Vac
systems. This unit easily
plugs into a
Square D
single-phase loadcenter
Type QO
®
and occupies
two 3/4-inch (19.1 mm)
pole spaces similar to a
two-pole Type QO breaker.
When installed properly, it
provides surge protection
for the entire loadcenter. If
internal components are
damaged, the CHQSA LED
visual indicators will signal
the need for a replacement.
This device is suitable for
service entrance locations
installed in accordance
with NEC guidelines. This
device is UL classified to
be used in place of Square D
Type QO surge arresters
(refer to Pub-23974)
Type BRSURGECSA
For use on single-phase
120/240 Vac systems. This
easily plugs into a single-
phase Type BR loadcenter
and occupies two 1-inch
(25.4 mm) pole spaces
similar to a two-pole Type
BR breaker. When installed
properly, it provides surge
protection for the entire
loadcenter. If internal
components are damaged,
the BRSURGECSA LED
visual indicators will signal
the need for replacement.
This device is suitable
for service entry locations
when installed in
accordance with Canadian
Electrical Code. This device
is CSA
®
listed to be used in
a Type BR loadcenter
Type 3 Point-of-Use Surge
Protection
Point-of-use surge protectors
such as surge receptacles
are installed within 30 ft of
conductor length from the
service panel and are
designed to offer premium
surge protection for specific
electronics while providing
innovative features to
enhance user convenience.
Standards and
Certifications
CHSPT1 Products: UL
1449 3rd Edition Type 1
CHSPT2 Products:
UL/cUL
®
1449 3rd Edition
Type 2
CHSPTELE: UL 497A, cUL
CHSPCABLE: UL 6500, cUL
NEMA
®
3R Enclosure for
CHSPTELE and
CHSPCABLE: UL 50
Enclosure
BRSURGE, CHSA,
BRSURGECSA, CHQSA:
UL 1449 3rd Edition plug-in
type; Type 2 SPD