Cut Sheet
V1-T2-4 Volume 1—Residential and Light Commercial CA08100002E—August 2015 www.eaton.com
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2.1
Surge Protection
Surge Protection Devices and Lightning Arresters
Product Selection
SPD Type 1 CHSP Service Entrance Surge Protection—UL 1449 3rd Edition
Product Features
●
Commercial grade AC power protection
●
Type 1 surge device for installation before or after the main service disconnect
●
Convenient mounting options—universal fit to any manufacturer’s equipment
●
Clear, visible LED indication displaying status of the surge protector
Accessory for Type 1 CHSP Service Entrance Surge Protection
Notes
1
MCOV: Maximum Continuous Operating Voltage that may be applied to the device per mode.
2
VPR: Voltage Protection Rating is the measured limiting voltage after a surge event.
3
I
n
: Nominal Discharge Current is the current that the device can withstand for 15 impulses.
4
SCCR: The amount of current the product can withstand under short-circuit conditions.
5
Surge Current Capacity: The maximum one time surge current rating per phase.
For warranty details, go to www.eaton.com/surgetrap.
Catalog
Number Connection Enclosure Voltage Phase
Frequency
(Hz) MCOV
1
VPR
2
I
n
3
SCCR
4
Surge Current
Capacity, Per
Phase Rating
5
CHSPT1ULTRA Permanently connected device
installed before or after the service
disconnect overcurrent device.
NEMA 4 100/200 Vac,
110/220 Vac,
120/240 Vac
Single 50/60 300 V L–L,
150 V L–N
1000 V L–L,
600 V L–N
20 kA 200 kA 50 kA
CHSPT1MAX Permanently connected device
installed before or after the service
disconnect overcurrent device.
NEMA 4 100/200 Vac,
110/220 Vac,
120/240 Vac
Single 50/60 300 V L–L,
150 V L–N
1000 V L–L,
600 V L–N
20 kA 200 kA 45 kA
CHSPT1MICRO Permanently connected device
installed before or after the service
disconnect overcurrent device.
NEMA 4 100/200 Vac,
110/220 Vac,
120/240 Vac
Single 50/60 300 V L–L,
150 V L–N
1000 V L–L,
600 V L–N
20 kA 200 kA 36 kA
CHSPT1-208Y Permanently connected device
installed before or after the service
disconnect overcurrent device.
NEMA 4 120/208 Vac Three-
phase
wye
50/60 300 V L–L,
150 V L–N
1000 V L–L,
600 V L–N
20 kA 200 kA 50 kA
Catalog
Number Description
SP1DINRAILKIT Mounting kit for wall or DIN rail installation.
CHSPT1ULTRA
CHSPT1MICRO
CHSPT1MAX
CHSPT1-208Y
SP1DINRAILKIT