2.1
Surge Protection
Surge Protection Devices and Lightning Arresters
SPD Type 2 CHSP Service Entrance Surge Protection—UL 1449 3rd Edition; cUL
Product Features
AC power protection
Universally connects to any manufacturer’s loadcenter (breaker box)
Quick connect design—easy to mount telephone and cable protection modules
LED status indication
Notes
1
MCOV: Maximum Continuous Operating Voltage that may be applied to the device per mode.
2
VPR: Voltage Protection Rating is the measured limiting voltage after a surge event.
3
I
n
: Nominal Discharge Current is the current that the device can withstand for 15 impulses.
4
SCCR: The amount of current the product can withstand under short-circuit conditions.
5
Surge Current Capacity: The maximum one time surge current rating per phase.
6
When used with a 50 A two-pole circuit breaker, 10 kA when used with a 15 A two-pole circuit breaker.
For warranty details, go to www.eaton.com/surgetrap.
Catalog
Number Connection Enclosure Voltage Phase
Frequency
(Hz) MCOV
1
VPR
2
I
n
3
SCCR
4
Surge Current
Capacity, Per
Phase Rating
5
CHSPT2ULTRA Can be attached to the outside of
any manufacturer’s loadcenter
(breaker box). This product should
be connected on the load side of
the loadcenter main service
disconnect through a dedicated
circuit breaker (follow NEC
Guidelines).
NEMA 4 120/240
Vac rated
line voltage
Single 60 150 V L–N,
300 V L–L
600 V L–N,
1000 V L–L,
800 V N–G,
600 V L–G
20 kA
6
22 kA 108 kA
(L1–N 54 kA, L1–G
54 kA, L2-N 54 kA,
L2–G 54 kA)
CHSPT2MAX Can be attached to the outside of
any manufacturer’s loadcenter
(breaker box). This product should
be connected on the load side of
the loadcenter main service
disconnect through a dedicated
circuit breaker (follow NEC
Guidelines).
NEMA 4 120/240
Vac rated
line voltage
Single 60 150 V L–N,
300 V L–L
600 V L–N,
1000 V L–L,
800 V N–G,
600 V L–G
10 kA 22 kA 72 kA
(L1–N 36 kA, L1–G
36 kA, L2–N 36 kA,
L2–G 36 kA)
CHSPT2MICRO Can be attached to the outside of
any manufacturer’s loadcenter
(breaker box). This product should
be connected on the load side of
the loadcenter main service
disconnect through a dedicated
circuit breaker (follow NEC
Guidelines).
NEMA 4 120/240
Vac rated
line voltage
Single 60 150 V L–N,
300 V L–L
600 V L–N,
1000 V L–L,
800 V N–G,
600 V L–G
5 kA 22 kA 36 kA
(L1–N 18 kA, L1–G
18 kA, L2–N 18 kA,
L2–G 18 kA)
CHSPT2ULTRA
CHSPT2MICRO
CHSPT2MAX