Surge Protection
Surge Protection Devices and Lightning Arresters
Type BR and CH Surge Breakers
Product Description
The CH and BR surge
breaker is designed to
provide premier AC power
surge protection for sensitive
electronics and appliances
from the damaging effects of
electrical surges. In addition,
the surge breaker is a
functional two-pole thermal
magnetic breaker.
The combination of circuit
protection and surge
protection provides extra
flexibility and space saving in
the loadcenter.
Product Features
Complete home surge
protection for all circuits
plus a functional two-pole
thermal magnetic breaker
LEDs provide protection
status
Plug-on connection to the
busbar provides superior
protection and easy
installation for new
construction or renovation
Eliminates the potential for
incorrect installation of
externally mounted surge
devices—(longer “lead”
lengths can reduce
protection levels)
Notes
1
Clamshell packaging available with CS modification code on the end of catalog number.
2
MCOV: Maximum Continuous Operating Voltage that may be applied to the device per mode.
3
VPR: Voltage Protection Rating is the measured limiting voltage after a surge event.
4
I
n
: Nominal Discharge Current is the current that the device can withstand for 15 impulses.
5
SCCR: The amount of current the product can withstand under short-circuit conditions.
6
Surge Current Capacity: The maximum one time surge current rating per phase.
Catalog
Number
1
Poles
Ampere
Rating Voltage Phase
Frequency
(Hz) MCOV
2
VPR
3
I
n
4
SCCR
5
Surge Current
Capacity, Per
Phase Rating
6
Type CH Surge Breakers
CH230SUR Two-pole
10 kAIC
30 120/240 Vac Single 50/60 150 V L–N,
300 V L–L
600 V L–N,
1000 V L–L
10 kA 10 kA 36 kA (L1–N 36 kA,
L2–N 36 kA)
CH250SUR 50 120/240 Vac Single 50/60 150 V L–N,
300 V L–L
600 V L–N,
1000 V L–L
10 kA 10 kA 36 kA (L1–N 36 kA,
L2–N 36 kA)
Type BR Surge Breakers
BR230SUR Two-pole
10 kAIC
30 120/240 Vac Single 50/60 150 V L–N,
300 V L–L
600 V L–N,
1000 V L–L
10 kA 10 kA 36 kA (L1–N 36 kA,
L2–N 36 kA)
BR250SUR 50 120/240 Vac Single 50/60 150 V L–N,
300 V L–L
600 V L–N,
1000 V L–L
10 kA 10 kA 36 kA (L1–N 36 kA,
L2–N 36 kA)
Type CH Surge
Breakers
Type BR Surge
Breakers