Loadcenters and Circuit Breakers
Loadcenter Interiors/OEM Loadcenters
Standards and Certifications
Class CTL
National Electrical Code
Paragraph 384.15 requires
branch circuit panelboards
to be provided with physical
means to prevent the
installation of more
overcurrent devices than
that number of which the
enclosure was designed,
rated and approved. Class
CTL Duplex, Quadplex and
twin breakers (identified
by a catalog number prefix
BD, BQ, BQC and CHT)
are equipped with a
UL listed rejection tab
over the line terminal.
All OEM interiors have
appropriately notched stabs
to accept these rejection
tab Class CTL breakers.
Duplex, Quadplex and twin
breakers manufactured
without the rejection tab
(identified by a catalog
number prefix BR, BRD
and CHT) are available
for replacement purposes
in older interiors.
Federal Specifications
All loadcenter enclosures
meet Federal Specifications
W-P-115b, Type 1, Class 2
requirements.
All 120/240 V breakers, both
1-inch (25.4 mm), 1/2-inch
(12.7 mm) and 3/4-inch
(19.1 mm) per pole meet
the requirement of Federal
Specifications W-C 375B/
Gen Type 1.
Canadian Standards
Association Listing
All single-pole and two-pole,
120/240 V breakers, both
1-inch (25.4 mm), 1/2-inch
(12.7 mm) and 3/4-inch
(19.1 mm) per pole, 225 A
maximum, are listed as
Certified by the Canadian
Standards Association, Guide
No. 69-11.19, Class 1432,
File 18328.
Underwriters
Laboratories Listing
All grounding bars
manufactured comply
with Underwriters
Laboratories standards
and are listed under
Guide No. DHJR, File
E31424, Volume W,
Section 17.
All circuit breakers 10 A
and larger comply with the
Underwriters Laboratories
“Standard for Branch
Circuit and Service Circuit-
Breakers” UL 489; Guide
No. 60 10.2 File E31424, and
“Requirements for Wire
Connectors and Soldering
Lugs,” UL 486B, Guide
No. 461 10-C File E7830.
All Eaton breakers where
marked, are suitable for use
with 60/75 °C rated wire,
unless otherwise specified.
All devices comply with the
22 kAIC–10 kAIC UL series
connected components File
DKSY2 of the Recognized
Components Index.
Lighting and
Appliance Panelboards
Lighting and appliance
branch circuit panelboards are
defined in NEC (Article 384)
as “One having more than
10 percent of its overcurrent
devices rated 30 A or less for
which neutral connections
are provided.” Article 384
also limits the number of
overcurrent devices (branch
circuit poles) to a maximum
of 42 in any one cabinet.
When the 42 poles are
exceeded, two or more
separate panels are required.
For more details and
engineering drawings,
see BR.31.02.S.E.
Product Selection
Type CH Loadcenter Interior Assemblies—Copper Bus
Ampere
Rating
Maximum Number 1-Inch (24.5 mm)
UL File
Reference
Main Terminal Size
(Per Phase)
Standard
Package Quantity
Catalog
NumberSpaces Single Poles
Single-Phase Single Row Breaker Mounting—120/240 Vac, Three-Wire
70 2 2 E8741 (1) #8–#2 AWG Cu/Al 1 CH9MB270
125 2 2 E8741 (1) 2/0–#6 AWG Cu/Al 20 CH2L125INT
Single-Phase Double Row Breaker Mounting—120/240 Vac, Three-Wire
125 4 4 E8741 (1) 2/0–#14 AWG Cu/Al 20 CH4L125INT
125 8 8 E8741 (1) 2/0–#6 AWG Cu/Al 20 CH8L125INT
125 12 12 E8741 (1) 2/0–#6 AWG Cu/Al 20 CH12L125INT
125 16 16 E8741 (1) 2/0–#6 AWG Cu/Al 20 CH16L125INT
200 12 12 E8741 (1) 300 kcmil–#4 AWG Cu/Al 20 CH12L200INT
200 16 16 E8741 (1) 300 kcmil–#4 AWG Cu/Al 10 CH16L200INT
225 24 24 E8741 (1) 300 kcmil–#4 AWG Cu/Al 10 CH24L225INT
225 32 32 E8741 (1) 300 kcmil–#4 AWG Cu/Al 10 CH32L225INT
225 42 42 E8741 (1) 300 kcmil–#4 AWG Cu/Al 10 CH42L225INT
Three-Phase Double Row Breaker Mounting—208Y/120 Vac, Four-Wire—240 Vac, Three-Wire—120/240 Vac, Four-Wire Delta
125 12 12 E8741 (1) 2/0–#6 AWG Cu/Al 10 CH12L3125INT
125 18 18 E8741 (1) 2/0–#6 AWG Cu/Al 10 CH18L3125INT
125 24 24 E8741 (1) 2/0–#6 AWG Cu/Al 10 CH24L3125INT
225 24 24 E8741 (1) 300 kcmil–#4 AWG Cu/Al 10 CH24L3225INT
225 30 30 E8741 (1) 300 kcmil–#4 AWG Cu/Al 10 CH30L3225INT
225 42 42 E8741 (1) 300 kcmil–#4 AWG Cu/Al 10 CH42L3225INT