Technical information
131Eaton RF-System
© 2013 Eaton Electrical Group
switching of an actuator.
FAQs
Why are there two different interfaces, CRSZ-00/01 and CKOZ-00/03?
The RS232 interface, CRSZ-00/01, is for commissioning the system in Comfort Mode via the MRF
software and is used solely for this purpose. The device is battery operated, but can also be
supplied or loaded by the mains unit provided.
Communications interface CKOZ-00/03 was specially developed for continuous stationary
operation and acts as an interface between the wireless system and other systems (PC, other bus
systems, etc). No external power supply is required when operating via USB. However, if the
interface is operated via the RS232 interface, a special RS232 set is required for operation
(CKOZ-00/04 or CKOZ-00/05).
Support
Please contact the following in the event of problems:
support@xcomfort.at
Analog input
The analog input is a mains-powered sensor and can control all xComfort actuators (switching
actuator, dimming actuator, shutter actuator, analog actuator) or it can send a measured value
(e.g. 0-100% according to settings) to the Home Manager, Room Manager or communications
interface.
As this is a mains-powered device, it is automatically detected when scanned providing that you
are within its reception range.
It has two inputs (Channel A, Channel B) for external sensors. 4 different input types can be
selected via the configuration window: 0-10 V, 0-20 mA, 4-20 mA und PT1000.
The measurement range for each channel can be set in the MRF for the respective device
(e.g. 0-10000...).
As for the room controller and temperature input, it can send a switching command, the converted
measured value over the measurement range or a direct percentage (0-100%, limits adjustable,
inversion option) if a set threshold is exceeded or not reached.
Both inputs (A und B) are independent from each other and can be treated separately.
Send switching command: