logic function.
Activating the option ‚Release Logic X‘ will enable the logic for configuration. You can chose the
desired logic operation (AND/OR/GREATER THAN/LOWER THAN/EQUAL), the input variables, a
hysteresis, a minimum time and the resulting action.
Generally all sensor output channels of existing xComfort channels can be used as input variables
of a logic (exception Binary input Mode 1 channels). Additionally one of the internal Markers or the
status of one of the 5 output channels can also be selected (if available).
Depending on the selection of the logic operation the second input variable can also be a fixed
value set by the user (only for analog logic operations).
For the comparison of analog values a hysteresis can be set (+/- 1/2 of the hysteresis value will be
used when comparing the input variables).
An optional minimum time will set how long the configured status needs to be active to execute the
resulting action.
If one of the 5 Logic outputs is used as output variable cyclic sending can be activated and the
cyclic time can be set between 1h and 18h.