Technical information
139Eaton RF-System
© 2013 Eaton Electrical Group
Impulse input:
The impulse input counts the impulses at its 2 separate S0 interfaces and forwards the readings to
a Room Manager with Energy function.
It features 2 separate channels independent from each other which can be configured by means of
the MRF.
Activate sending: Here you can select whether or not the value counted for this channel should be
transmitted.
Send all cyclically: Here the cycle time for transmission can be set between 10 minutes and 1 hour.
The impulse input has two 32 bit counters (1 for each channel) and counts all impulses at its S0
inputs in absolute figures until they are reset or until they are supposed to run over.
The maximum counting frequency of the impulses is defined in the Standard for S0 interfaces, it is
16 Hz.
All the other settings, such as the unit of the variable to be measured or the counting constant of
the connected counter can be done at the Room Manager, in the Settings window for the Energy
input.
Also refer to chapter Room Manager with Energy function – Input with Impulse input
Remote Control with Display
The Remote Control with Display is a 12-channel remote control with LCD display and a timer
function for up to 3 timers.