Technical information

196 Eaton RF-System - Help
© 2013 Eaton Electrical Group
Then confirm with OK.
Result: If the adjustment wheel is set to zero and the temperature is 25°C, the room controller
sends the command “below” to the switching actuator. It is not until a temperature of 24°C (as
the hysteresis is 1°C) is reached that it sends “beyond” .
The reaction depends on the configuration of the switching actuator.
Sending a temperature value:
The room controller is supposed to send a temperature value to the Home Manager (cyclically,
every 10 minutes).
Select the desired mode, and by means of the slider control, select Send cyclically every 10
minutes.
Then confirm with OK.