Technical information
87Eaton RF-System
© 2013 Eaton Electrical Group
Heating and cooling with the Room Manager (Room 1 to 3)
You can define up to 6 rooms/temperature zones for heating and/or cooling in the Room Manager.
For a fully functional room control you need at least one device for temperature measurement and
one heating/cooling actuator.
Room 1 is always active because the room temperature is measured by the internal temperature
sensor of the Room Manager. When another room controller or temperature input is assigned to
the Room Manager you can select if this sensor is used for room temperature/humidity
measurement (Room 1 to 6) or only used as an input.
Once a temperature sensor and a heating/cooling actuator is assigned the room can be
configured. You can change the set points for the temperature of every operation mode for heating
and for cooling as well (if cooling actuator is assigned).
At „optimize Switch-ON time“ you set the time lag of the room. You have 3 different selection
possibilities (fast, middle, slow).
To prevent an oscillation of the heating/cooling every set point has a fix hysteresis of 0.3°C.
If you have a set point of 22°C the heating is activated until it reaches 22°C. At 22°C it switches
Off. If the temperature falls down below 21.7°C the heating is switched On again.
You can also set a timer programme for the operation mode comfort or standby for every room.