Firmware Manual

Chapter 7—Multi-PID Application
PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com 91
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
P10.14
12
PID1 Set Point 1 Source 1 1312 0 = Not Used
1 = PID1 Keypad Set Point 1
2 = PID1 Keypad Set Point 2
3 = AI1
4 = AI2
5 = Slot A: AI1
6 = Slot B: AI1
7 = FB Data Input 1
8 = FB Data Input 2
9 = FB Data Input 3
10 = FB Data Input 4
11 = FB Data Input 5
12 = FB Data Input 6
13 = FB Data Input 7
14 = FB Data Input 8
P10.15
2
PID1 Set Point 1 Min –200.00 200.00 % 0.00 1313
P10.16
2
PID1 Set Point 1 Max –200.00 200.00 % 100.00 1314
P10.17
12
PID1 Set Point 1 Sleep
Enable
0 1315 0 = Disabled
1 = Enabled
P10.18
2
PID1 Set Point 1 Sleep Freq 0.00 400.00 Hz 0.00 1316
P10.19
2
PID1 Set Point 1 Sleep Delay 0 3000 s 0 1317
P10.20
2
PID1 Set Point 1 Wake Up
Level
Par. P10.5 Par. P10.6 Varies 0.00 1318
P10.21
2
PID1 Set Point 1 Boost –2.0 2.0 1.0 1320
P10.22
12
PID1 Set Point 2 Source 2 1321 See P10.14
P10.23
2
PID1 Set Point 2 Min –200.00 200.00 % 0.00 1322
P10.24
2
PID1 Set Point 2 Max –200.00 200.00 % 100.00 1323
P10.25
12
PID1 Set Point 2 Sleep
Enable
0 1324 0 = Disabled
1 = Enabled
P10.26
2
PID1 Set Point 2 Sleep Freq 0.00 400.00 Hz 0.00 1325
P10.27
2
PID1 Set Point 2 Sleep Delay 0 3000 s 0 1326
P10.28
2
PID1 Set Point 2 Wake Up
Level
Par. P10.5 Par. P10.6 Varies 0.00 1327
P10.29
2
PID1 Set Point 2 Boost –2.0 2.0 1.0 1329
P10.30
12
PID1 Feedback Function 0 1330 0 = Source 1
1 = SQRT(Source 1)
2 = SQRT(Source 1–Source 2)
3 = SQRT(Source 1) +
SQRT(Source 2)
4 = Source 1 + Source 2
5 = Source 1–Source 2
6 = MIN(Source 1,Source 2)
7 = MAX(Source 1,Source 2)
8 = MEAN(Source1,Source2)
P10.31
2
PID1 Feedback Gain –1000.0 1000.0 % 100.0 1331
Table 73. PID Controller 1—P10, continued
Code Parameter Min. Max. Unit Default ID Note