Firmware Manual

Chapter 7—Multi-PID Application
98 PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Table 84. BACnet MS/TP—P20.2
Code Parameter Min. Max. Unit Default ID Note
P20.2.11 BACnet Baud Rate 2 594 0 = 9600
1 = 19200
2 = 38400
3 = 76800
4 = 115200
P20.2.12 MAC Address 0 127 1 595
P20.2.13 Instance Number 0 4194302 0 596
P20.2.14 Comm Timeout BACnet ms 6000 598
P20.2.15 Protocol Status 0 599 0 = Stopped
1 = Operational
2 = Faulted
P20.2.16 Fault Code 0 600 0 = None
1 = Sole Master
Table 85. EtherNet/IP / Modbus TCP—P20.3
Code Parameter Min. Max. Unit Default ID Note
P20.3.1 IP Address Mode 1 1500 0 = Static IP
1 = DHCP with AutoIP
P20.3.2 Active IP Address 1507
P20.3.3 Active Subnet Mask 1509
P20.3.4 Active Default Gateway 1511
P20.3.5 MAC Address 1513
P20.3.6 Static IP Address 192.168.1.254 1501
P20.3.7 Static Subnet Mask 255.255.255.0 1503
P20.3.8 Static Default Gateway 192.168.1.1 1505
P20.3.9 EtherNet/IP Protocol Status 0 608 0 = Stopped
1 = Operational
2 = Faulted
P20.3.10 Connection Limit 0 2 2 609
P20.3.11 Modbus TCP Unit ID 1 610
P20.3.12 Comm Timeout Modbus TCP ms 2000 611
P20.3.13 Protocol Status 0 612 0 = Stopped
1 = Operational
2 = Faulted
P20.3.14 Slave Busy 0 613 0 = Not Busy
1 = Busy
Note: Codes P20.3.15–P20.3.17 are for Modbus TCP.
P20.3.15 Parity Error 0 614
P20.3.16 Slave Failure 0 615
P20.3.17 Last Fault Response 0 616