Firmware Manual

Chapter 8—Multi-Purpose Application
122 PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Table 103. PID Controller 2—P11
Code Parameter Min. Max. Unit Default ID Note
P11.1
2
PID2 Control Gain 0.00 200.00 % 100.00 1356
P11.2
2
PID2 Control I Time 0.00 600.00 s 1.00 1357
P11.3
2
PID2 Control D Time 0.00 100.00 s 0.00 1358
P11.4
12
PID2 Process Unit 0 1359 See P10.4
P11.5
2
PID2 Process Unit Min –99999.99 99999.99 Varies 0.00 1360
P11.6
2
PID2 Process Unit Max –99999.99 99999.99 Varies 100.00 1362
P11.7
2
PID2 Process Unit Decimal 0 4 2 1364
P11.8
12
PID2 Error Inversion 0 1365 See P2.6
P11.9
2
PID2 Dead Band 0.00 99999.99 Varies 0.00 1366
P11.10
2
PID2 Dead Band Delay 0.00 320.00 s 0.00 1368
P11.11
2
PID2 Keypad Set Point 1 Par. P11.5 Par. P11.6 Varies 0.00 1369
P11.12
2
PID2 Keypad Set Point 2 Par. P11.5 Par. P11.6 Varies 0.00 1371
P11.13
2
PID2 Ramp Time 0.00 300.00 s 0.00 1373
P11.14
12
PID2 Set Point 1 Source 1 1374 See P10.14
P11.15
2
PID2 Set Point 1 Min –200.00 200.00 % 0.00 1375
P11.16
2
PID2 Set Point 1 Max –200.00 200.00 % 100.00 1376
P11.17
12
PID2 Set Point 1 Sleep
Enable
0 1377 0 = Disabled
1 = Enabled
P11.18
2
PID2 Set Point 1 Sleep Freq 0.00 400.00 Hz 0.00 1378
P11.19
2
PID2 Set Point 1 Sleep Delay 0 3000 s 0 1379
P11.20
2
PID2 Set Point 1 WakeUp
Level
Par. P11.5 Par. P11.6 Varies 0.00 1380
P11.21
2
PID2 Set Point 1 Boost –2.0 2.0 1.0 1382
P11.22
12
PID2 Set Point 2 Source 2 1383 See P10.14
P11.23
2
PID2 Set Point 2 Min –200.00 200.00 % 0.00 1384
P11.24
2
PID2 Set Point 2 Max –200.00 200.00 % 100.00 1385
P11.25
12
PID2 Set Point 2 Sleep
Enable
0 1386 0 = Disabled
1 = Enabled
P11.26
2
PID2 Set Point 2 Sleep Freq 0.00 400.00 Hz 0.00 1387
P11.27
2
PID2 Set Point 2 Sleep Delay 0 3000 s 0 1388
P11.28
2
PID2 Set Point 2 WakeUp
Level
Par. P11.5 Par. P11.6 Varies 0.00 1389
P11.29
2
PID2 Set Point 2 Boost –2.0 2.0 1.0 1391
P11.30
12
PID2 Feedback Func 0 1392 See P10.30
P11.31
2
PID2 Feedback Gain –1000.0 1000.0 % 100.0 1393
P11.32
12
PID2 Feedback 1 Source 1 1394 See P10.32
P11.33
2
PID2 Feedback 1 Min –200.00 200.00 % 0.00 1395
P11.34
2
PID2 Feedback 1 Max –200.00 200.00 % 100.00 1396
P11.35
12
PID2 Feedback 2 Source 0 1397 See P10.32
P11.36
2
PID2 Feedback 2 Min –200.00 200.00 % 0.00 1398
P11.37
2
PID2 Feedback 2 Max –200.00 200.00 % 100.00 1399
P11.38
12
PID2 Feedforward Func 0 1400 See P10.38
P11.39
2
PID2 Feedforward Gain –1000.0 1000.0 % 100.0 1401
P11.40
12
PID2 Feedforward 1 Source 0 1402 See P10.40
P11.41
2
PID2 Feedforward 1 Min –200.00 200.00 % 0.00 1403