P8.39 1622 Start Boost Rise Time 1,2,3,4 RW
Acceleration time used with auto torque boost.
P8.40 1623 Flux Current Ramp Time 4 RW
Time to use the flux ramp level when advanced motor control is needed.
P8.41 1624 Zero Speed Start Time 4 RW
Zero speed delay time when starting the motor.
P8.42 1625 Zero Speed Stop Time 4 RW
Zero speed delay time when stopping the motor.
P8.43 1630 Droop Control Filter Time Constant 4 RW
Filter time when using droop control.
P8.44 1631 Start Torque Selection 4 RW
Selects where the startup torque reference comes from (either Start Memory,
Torque Reference, and Start Torque FWD/REV).
P8.45 1632 Start Memory Start 4 RW
Torque value is stored in memory. If you look at P8.47, you can select where the
torque on startup is given from. This is a preset value for both forward and reverse if
both are required to be equal.
P8.46 1633 Start Torque Forward 4 RW
Selects the amount of starting torque in the Forward direction.
P8.47 1634 Start Torque Reverse 4 RW
Selects the amount of starting torque Reverse direction.
P8.48 1635 Start Torque Actual 4 RW
Actual start torque.
P8.49 1667 Startup Torque Time 4 RW
This is the amount of time that the startup torque boost is active in either forward or
reverse during startup.
P8.50 771 Stator Resistor 4 RW
Motor stator resistor real value. This value is the stator winding resistance of the
windings in the motor. Value is measured when performing Identification (P8.14).
P8.51 772 Rotor Resistor 4 RW
Motor rotor resistor real value. This value is the rotor resistance of the motor. Value
is measured when performing Identification (P8.14).
P8.52 773 Leak Inductance 4 RW
Motor leakage inductance real value. This value is the amount of magnetic
inductance that does not link to a winding in the motor. Value is measured when
performing Identification (P8.14).
P8.53 774 Mutual Inductance 4 RW
Motor mutual inductance real value. This value is the amount of inductance between
2 sets of windings in the motor. Value is measured when performing Identification
(P8.14).
P8.54 775 Excitation Current 4 RW
Motor no-load current real value. This value is the amount of electrical current
required to generate a rotating magnetic field in the motor. Value is measured when
performing Identification (P8.14).