Firmware Manual

Appendix A—Description of Parameters
176 PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com
P13.11 1666 Torque Control Freq Max 4 RW
With this parameter, the maximum frequency for the torque control can be selected.
0 Maximum frequency, P1.2
1 Selected frequency reference
2 Preset speed 7, P12.7
P13.12 1636 Window Pos Width 4 RW
Positive torque control width.
P13.13 1637 Window Neg Width 4 RW
Negative torque control width.
P13.14 1638 Window Pos Off Limit 4 RW
Positive torque off limit.
P13.15 1639 Window Neg Off Limit 4 RW
Negative torque off limit.
P13.16 1640 Torque Reference Filter TC 4 RW
Torque reference filter time.
P13.17 1606 Pull Out Torque 4 RW
Startup torque level in percentage.
P13.18 1667 Startup Torque Time 4 RW
Startup torque time limit for starting torque level in open loop torque control mode.
P13.19 1684 Stop State Magnetization Time 4 RW
Motor stop magnetization time upon stopping in open loop torque control mode.
P14.1 254 DC-Brake Current 1, 2, 3, 4 RW
Defines the current injected into the motor during DC-braking.
P14.2 263 Start DC-Brake Time 1, 2, 3, 4 RW
DC-brake is activated when the start command is given. This parameter defines the
time before the brake is released. After the brake is released, the output frequency
increases according to the set start function by P7.9.
P14.3 262 Stop DC-Brake Frequency 1, 2, 3, 4 RW
The output frequency at which the DC-braking is applied on stopping. See Figure 66.
Code Modbus ID Parameter Application
RO/RW