Quick Start Guide

Step 5Standard Parameter List
PowerXL DG1 Series Adjustable Frequency Drives MN040012EN—March 2014 www.eaton.com 13
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Table 8. Operate Mode—O
Code Parameter Min. Max. Unit Default ID Note
O1 Output Frequency Hz 0.00 1
O2 Freq Reference Hz 0.00 24
O3 Motor Speed rpm 0 2
O4 Motor Current A 0.0 3
O5 Motor Torque % 0.0 4
O6 Motor Power % 0.0 5
O7 Motor Voltage V 0.0 6
O8 DC-link Voltage V 0 7
O9 Unit Temperature °C 0.0 8
O10 Motor Temperature % 0.0 9
R12
2
Keypad Reference Par. P1.1 Par. P1.2 Hz 0.00 141
Table 9. Basic Parameters—P1
Code Parameter Min. Max. Unit Default ID Note
P1.1
2
Min Frequency 0.00 Par. P1.2 Hz 0.00 101
P1.2
2
Max Frequency Par. P1.1 400.00 Hz Max Freq 102
P1.3
2
Accel Time 1 0.1 3000.0 s 3.0 103
P1.4
2
Decel Time 1 0.1 3000.0 s 3.0 104
P1.5
1
Motor Nom Current Drive Nom
CT*1/10
Drive Nom
CT*2
A Drive Nom CT 486
P1.6
1
Motor Nom Speed 300 20000 rpm Motor Nom Speed 489
P1.7
1
Motor PF 0.30 1.00 0.85 490
P1.8
1
Motor Nom Voltage 180 690 V Motor Nom Voltage 487
P1.9
1
Motor Nom Frequency 8.00 400.00 Hz Motor Nom Freq 488
P1.10
2
Local/Remote Select 0 140 0 = Hold Last
1 = Local Control
2 = Remote Control
P1.11
2
Remote1 Control Place 0 135 0 = I/O Terminal
1 = Fieldbus
P1.12 Local Control Place 0 1695 0 = Keypad
1 = I/O Terminal