Quick Start Guide

Step 5Standard Parameter List
PowerXL DG1 Series Adjustable Frequency Drives MN040012EN—March 2014 www.eaton.com 21
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
P9.32
2
External Fault Attempts 0 10 0 328
P9.33
2
Underload Attempts 0 10 1 336
P9.34
12
RTC Fault 1 955 See P9.11
P9.35
12
PT100 Fault Response 2 337 See P9.11
P9.36
12
Replace Battery Fault
Response
1 1256 See P9.11
P9.37
12
Replace Fan Fault Response 1 1257 See P9.11
P9.38
12
IP Address Confliction Resp 1 1678 See P9.11
P9.39 Cold Weather Mode 0 1 0 2126 0 = No
1 = Yes
P9.40 Cold Weather Voltage Level 0 20 % 2 2127
P9.41 Cold Weather Time Out 0 10 min 3 2128
P9.42 Cold Weather Password 2129
P9.43 Under Temp Fault Override 0 1 0 2130 0 = No
1 = Yes
Table 17. Preset Speed—P12
Code Parameter Min. Max. Unit Default ID Note
P12.1
2
Preset Speed 1 0.00 Par. P1.2 Hz 5.00 105
P12.2
2
Preset Speed 2 0.00 Par. P1.2 Hz 10.00 106
P12.3
2
Preset Speed 3 0.00 Par. P1.2 Hz 15.00 118
P12.4
2
Preset Speed 4 0.00 Par. P1.2 Hz 20.00 119
P12.5
2
Preset Speed 5 0.00 Par. P1.2 Hz 25.00 120
P12.6
2
Preset Speed 6 0.00 Par. P1.2 Hz 30.00 121
P12.7
2
Preset Speed 7 0.00 Par. P1.2 Hz 35.00 122
Table 18. Brake—P14
Code Parameter Min. Max. Unit Default ID Note
P14.1
12
DC-Brake Current Drive Nom
CT*15/100
Drive Nom
CT*15/10
ADrive Nom
CT*1/2
254
P14.2
12
Start DC-Brake Time 0.00 600.00 s 0.00 263
P14.3
12
Stop DC-Brake Frequency 0.10 10.00 Hz 1.50 262
P14.4
12
Stop DC-Brake Time 0.00 600.00 s 0.00 255
P14.5
12
Brake Chopper 0 251 0 = Disabled
1 = B(Run) T(Rdy)
2 = External
3 = B(Rdy) T(Rdy)
4 = B(Run) T(No)
P14.6
12
Flux Brake 0 266 0 = Off
1 = On
P14.7
12
Flux Brake Current Active Motor
Nom I*1/10
Par. P8.2 A Active Motor
Nom I*1/2
265