Assembly Instance 127
Table 94. Instance 127 (Input). EIP Drive Status Length = 20 bytes
1
FBStatusWord.
2
This is the actual value from the frequency converter. The value is between 0 and 10000. In the
application, the value is scaled in percentage of frequency area between set minimum and maximum
frequency. (0 = 0.00%–10000 = 100.00%).
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
0 FBStatusWord (Low Byte)
1
1 FBStatusWord (High Byte)
1
2 % Speed Actual (Low Byte)
2
3 % Speed Actual (High Byte)
2
4 ProcessDataOut1 (LowByte)
5 ProcessDataOut1 (HighByte)
6 ProcessDataOut2 (LowByte)
7 ProcessDataOut2 (HighByte)
8 ProcessDataOut3 (LowByte)
9 ProcessDataOut3 (HighByte)
10 ProcessDataOut4 (LowByte)
11 ProcessDataOut4 (HighByte)
12 ProcessDataOut5 (LowByte)
13 ProcessDataOut5 (HighByte)
14 ProcessDataOut6 (LowByte)
15 ProcessDataOut6 (HighByte)
16 ProcessDataOut7 (LowByte)
17 ProcessDataOut7 (HighByte)
18 ProcessDataOut8 (LowByte)
19 ProcessDataOut8 (HighByte)
Bit Description (Value = 0) Description (Value = 1)
0 Not ready Ready
1Stop Run
2 Clockwise Counter-clockwise
3 No fault Faulted
4No alarm Alarm
5 Ref. Freq. not reached Ref. Freq. reached
6 Motor not running at zero speed Motor running at zero speed
7–15 Not in use