Specification

CORE Lighting Controls
5. DEVINE Fan-Speed Controls:
a. Fan-speed controls shall be cULus Listed and NOM approved, DEVINE style.
b. Quiet fan-speed model (DFS15P) shall provide three speed settings with paddle providing preset on
and off.
c. Quiet fan-speed control shall provide single-pole/3-way control of one paddle fan (1.5A max.).
B. DEVINE Accessories
1. Switch Components
a. Switches shall provide on/off control of any 120/277 VAC load up to 15A or 20A.
b. Switches shall be UL Listed as general-use AC switches
c. Switches shall be available in single-pole (7501), 3-way (7503), and 4-way (7504) configurations.
d. Single-pole (7511), 3-way (7513) and 4-way (7514) switches will also be available in lighted
versions.
C. Screwless Wallplates
1. Wallplates shall be manufactured from durable polycarbonate plastic with gloss finish, and shall attach to
the basic components without using exposed hardware or screws.
2. Multigang wallplates shall provide a continuous, seamless cover for up to six-ganged (PJS26, PJS262,
PJS263, PJS264, PJS265, PJS266) decorator-style control and accessory combinations with no exposed
hardware or screws.
4. Multigang wallplates shall include an adapter plate for proper device alignment and wallplate attachment.
5. Control, accessory and wallplate profiles shall not exceed .30 inches from wall surface to faceplate front
surface.
6. To ensure a precise color match between all plastic parts, color variation of any gloss finish control or
wallplate shall not exceed a delta E of 1, CIE L*a*b* color units, as defined in ASTM E 308-99.
7. Visible parts of dimmers, switches, standard receptacles, cable jacks or any wallplate shall exhibit ultraviolet
stability when tested with multiple actinic light sources as defined in ASTM D4674-89.
2.03 SOURCE QUALITY CONTROL
A. All controls shall be 100% functionally tested at the time of manufacture. Statistical sampling plan shall not be
acceptable.
PART 3 — EXECUTION
3.01 INSTALLATION
A. Contractor shall furnish all devices, labor and other services necessary for the proper installation of the devices as
indicated on the drawings and specified herein.
B. Contractor shall be responsible for de-rating lighting controls capacity in multi-gang installations.
C. Devices shall be installed utilizing manufacturer’s recommended application, wiring and installation instructions.
D. Contractor shall provide frameless wallplate covers per specification 2.02 for all devices ganged in a common box.
Contractor shall provide barriers within the box where required by code.
3.02 FIELD QUALITY CONTROL
A. Cooper Wiring Devices technical hotline available 8:00AM–6:00PM E.S.T. Monday–Friday: 1-866-853-4293
B. Supplemental information shall be provided on the Cooper Wiring Device website at www.cooperwiringdevices.com
Cooper Wiring Devices is a valuable trademark of Cooper Industries in the U.S. and other countries. You are not permitted to use
the Cooper Trademarks without the prior written consent of Cooper Industries.