Datasheet

3 100 V A 1.5
3 220 V A 0.5
Conv. thermal current I
th
A 10
Control circuit reliability Failure rate λ
<10
-8
, < one failure at 100 million operations
(at U
e
= 24 V DC, U
min
= 17 V, I
min
= 5.4 mA)
Component lifespan at U
e
= 240 V
AC-15 Operations
x 10
6
0.2
DC current
L/R = 50 ms: 2 contacts in series at I
e
= 0.5 A Operations
x 10
6
0.15
Notes Switch-on and switch-off conditions based on DC-13, time constant as specified
Short-circuit rating without welding
Maximum overcurrent protective device
Short-circuit protection only PKZM0-4
Short-circuit protection maximum fuse
500 V A gG/gL 6
500 V A fast 10
Current heat loss at a load of I
th
per contact W 1.1
Rating data for approved types
Switching capacity
Maximum motor rating
Three-phase
200 V
208 V
HP 1.5
230 V
240 V
HP 2
460 V
480 V
HP 3
575 V
600 V
HP 3
Single-phase
115 V
120 V
HP 0.25
230 V
240 V
HP 1
General use A 15
Auxiliary contacts
Pilot Duty
AC operated A600
DC operated P300
General Use
AC V 600
AC A 10
DC V 250
DC A 0.5
Short Circuit Current Rating SCCR
Basic Rating
SCCR kA 5
max. Fuse A 45
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 6.6
Heat dissipation per pole, current-dependent P
vid
W 0.2
Equipment heat dissipation, current-dependent P
vid
W 0.6
Static heat dissipation, non-current-dependent P
vs
W 2.3
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
12/27/2018 Eaton 051650 ED2018 V51.0 EN 5 / 10