Datasheet

Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Open °C -25 - +50
Enclosed °C - 25 - 40
Storage °C
Min. ambient temperature, storage °C - 40
Ambient temperature, storage max. °C + 80
Mounting position As required, except vertical with terminals A1/A2 at the bottom
Mounting position
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 10 ms
Basic unit without auxiliary contact module
Main contacts, make contacts g 10
Main contacts Make/break contacts g
Break contact g 10
Basic unit with auxiliary contact module
Main contacts make contact g
Make g 10
Auxiliary contacts Make/break contacts g 20 / 20
Degree of Protection IP20
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Weight kg 0.17
Terminal capacity of auxiliary and main contacts
Spring-loaded terminals
Flexible with ferrule
mm
2
1 x (1 - 2.5)
2 x (1 - 2.5)
Solid or stranded AWG 16 - 14
Stripping length mm 10
Standard screwdriver mm 0.6 x 3.5
Main conducting paths
Rated impulse withstand voltage U
imp
V AC 6000
Overvoltage category/pollution degree III/3
Rated insulation voltage U
i
V AC 690
Rated operational voltage U
e
V AC 690
Safe isolation to EN 61140
between coil and contacts V AC 300
between the contacts V AC 300
Making capacity (cos ϕ to IEC/EN 60947) A 110
Breaking capacity
220 V 230 V A 90
380 V 400 V A 90
500 V A 64
660 V 690 V A 42
Short-circuit protection maximum fuse
Type ”2”, 500 V gL/gG A 10
Type ”1”, 500 V gL/gG A 20
12/27/2018 Eaton 230166 ED2018 V51.0 EN 2 / 11