Datasheet

DATASHEET - DILEM-10-G-C(24VDC)
Contactor, 3p+1N/O, 4kW/400V/AC3
Part no. DILEM-10-G-C(24VDC)
Catalog No. 230165
Eaton Catalog No. XTMCC9A10TD
Delivery program
Product range Contactors
Application Mini Contactors for Motors and Resistive Loads
Subrange DILEM contactors
Utilization category AC-1: Non-inductive or slightly inductive loads, resistance furnaces
NAC-3: Normal AC induction motors: starting, switch off during running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Notes Also suitable for motors with efficiency class IE3.
IE3-ready devices are identified by the logo on their packaging.
Connection technique Spring-loaded terminals
Description With auxiliary contact
Number of poles 3 pole
Rated operational current
AC-3
380 V 400 V I
e
A 9
AC-1
Conventional free air thermal current, 3 pole, 50 - 60 Hz
Open
at 40 °C I
th
=I
e
A 22
Max. rating for three-phase motors, 50 - 60 Hz
AC-3
220 V 230 V P kW 2.2
380 V 400 V P kW 4
660 V 690 V P kW 4
AC-4
220 V 230 V P kW 1.5
380 V 400 V P kW 3
660 V 690 V P kW 3
Contacts
N/O = Normally open 1 N/O
Contact sequence
For use with …DILEM-C
…DILE-C
Actuating voltage 24 V DC
Voltage AC/DC DC operation
Technical data
General
Standards IEC/EN 60947, VDE 0660, CSA, UL
Lifespan, mechanical Operations
x 10
6
20
Maximum operating frequency
Mechanical Ops./h 9000
electrical (Contactors without overload relay) Operations/h Page 05/070
Climatic proofing Damp heat, constant, to IEC 60068-2-78
12/27/2018 Eaton 230165 ED2018 V51.0 EN 1 / 11