Datasheet

DATASHEET - DILMC32-01(RDC24)
Contactor, 3p+1N/C, 15kW/400V/AC3
Part no. DILMC32-01(RDC24)
Catalog No. 277745
Eaton Catalog No. XTCEC032C01TD
EL-Nummer
(Norway)
0004110332
Delivery program
Product range Contactors
Application Contactors for Motors
Subrange Contactors up to 170 A, 3 pole
Utilization category AC-1: Non-inductive or slightly inductive loads, resistance furnaces
NAC-3: Normal AC induction motors: starting, switch off during running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Notes Also suitable for motors with efficiency class IE3.
IE3-ready devices are identified by the logo on their packaging.
Connection technique Spring-loaded terminals
Description Spring-cage terminals on auxiliary and control circuit terminals
Number of poles 3 pole
Rated operational current
AC-3
380 V 400 V I
e
A 32
AC-1
Conventional free air thermal current, 3 pole, 50 - 60 Hz
Open
at 40 °C I
th
=I
e
A 45
enclosed I
th
A 36
Conventional free air thermal current, 1 pole
open I
th
A 100
enclosed I
th
A 90
Max. rating for three-phase motors, 50 - 60 Hz
AC-3
220 V 230 V P kW 10
380 V 400 V P kW 15
660 V 690 V P kW 17
AC-4
220 V 230 V P kW 4
380 V 400 V P kW 7
660 V 690 V P kW 10
Contacts
N/C = Normally closed 1 NC
Contact sequence
Instructions Contacts to EN 50 012.
Auxiliary current, coil connections with spring-cage connection technology.
Main current connections with screw terminals.
integrated suppressor circuit in actuating electronics
with mirror contact.
Can be combined with auxiliary contact DILA-XHIC(V)..
Actuating voltage RDC 24: 24 - 27 V DC
Voltage AC/DC DC operation
Connection to SmartWire-DT yes
12/28/2018 Eaton 277745 ED2018 V51.0 EN 1 / 14