Contents 1. Safety and EMC Instructions .............................................................................................................1-3 1.1 Installation........................................................................................................................................ 1 1.2 Operation ......................................................................................................................................... 2 1.3 Maintenance, Servicing and Faults.............
14. Trouble Shooting ............................................................................................................................... 27 15. Operating Mode for all Models ....................................................................................................28-29 16. Communication Port ......................................................................................................................... 30 17. Software for all models……………………………………………………………………………………. .31 18.
1. Safety and EMC instructions Please read carefully the following user manual and the safety instructions before installing the unit or using the unit! This manual is designed for the product that the model designation rules as followed: Eaton E Series DX 1000H (X) (XL) Brand name Code Nil UPS series XL Output capacity(VA) Code B I ...
◇ For 6000H / 10000H ★ UPS has provided earthed terminal, in the final installed system configuration, equipotential earth bonding to the external UPS battery cabinets. ★ An integral single emergency switching device which prevents further supply to the load by the UPS in any mode of operation should be provided in the building wiring installation. ★ An appropriate disconnect device as short-circuit backup protection should be provided in the building wiring installation.
Hazardous voltages may occur between the battery terminals and the ground. Verify that no voltage is present before servicing! ★ Batteries have a high short-circuit current and pose a risk of shock. Take all precautionary measures specified below and any other measures necessary when working with batteries: - remove all jewellery, wristwatches, rings and other metal objects - use only tools with insulated grips and handles.
◇ For 6000H(XL) / 10000H(XL) * Safety IEC/EN 62040-1-1 * EMI Conducted Emission.................................:IEC/EN 50091-2 Radiated Emission....................................:IEC/EN 50091-2 * EMS ESD.......................................................:IEC/EN 61000-4-2 RS.........................................................:IEC/EN 61000-4-3 EFT........................................................:IEC/EN 61000-4-4 SURGE.................................................
3. Introduction – 1000H(XL)/2000H(XL)/3000H(XL) This On-Line-Series is an uninterruptible power supply incorporating double-converter technology. It provides perfect protection specifically for Novell, Windows NT and UNIX servers. The double-converter principle eliminates all mains power disturbances. A rectifier converts the alternating current from the socket outlet to direct current. This direct current charges the batteries and powers the inverter.
4. System Description Figure 1: Display Panel Switch ON - Switch OFF-Switch Display LINE LED BATTERY LED BYPASS LED INVERTER LED FAULT LED Function Turn on UPS system: By pressing the ON-Switch “I” the UPS system is turned on. Deactivate acoustic alarm: By pressing this switch an acoustic alarm can be deactivated. When mains power is normal, the UPS system switches to Standby mode by pressing OFF-Switch “ “. It is then switched to Bypass and the inverter is off.
5. Connection and Operation The system may be installed and wired only by qualified electricians in accordance with applicable safety regulations! 5.1 Connection and operation for 1000H(XL)/ 2000H(XL)/ 3000H(XL) When installing the electrical wiring, please note the nominal amperage of your incoming feeder 1) Inspection: Inspect the packaging carton and its contents for damage. Please inform the transport agency immediately should you find signs of damage.
5. Connection and Operation Figure 2: Connection diagram of 2000HXL(CE) and 3000H(XL) 2.3) Computer Connection: Connect your computer to the outlet sockets of the UPS system following the above diagram. Caution! *Do not connect equipment which would overload the UPS system (e.g. laser printers) 3) Battery Charge: Fully charge the batteries of the UPS system by leaving the UPS system connected to the mains for 1-2 hours.
5. Connection and Operation 6) Turn Off the UPS: 6.1) In Inverter Mode: Press “ “ button continuously for more than 1 second to turn off the UPS. Then the UPS will get into self-test status first. After having finished the self-test, the UPS will get into bypass mode and the Utility Power LED and Bypass LED will light up. At this time, the UPS might has output. Disconnect the utility power to turn off the output. 6.2) In Battery Mode: Press “ “ button continuously for more than 1 second to turn off the UPS.
5. Connection and Operation (6) The "+" terminal of the battery. The black wire is connected to the "-" terminal of the battery. (Note: the green/yellow wire is grounded for protection purpose.) (7) Do not connect the UPS to any load yet. Then, connect the power cord of the UPS to supply utility power to the UPS to make the UPS operation in utility power mode.
6. Trouble Shooting If the UPS system does not operate correctly, please attempt to solve the problem using the table below. Problem No indication, no warning tone even Possible cause No input voltage though system is connected to Remedy Check building wiring socket outlet and input cable. mains power supply LINE LED blinks Phase and neutral Rotate mains power socket by 180° or connect conductor at input of UPS UPS system.
7. Maintenance 7.1 Operation The UPS system contains no user-serviceable parts. If the battery service life (3 - 5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case please contact your dealer. 7.2 Storage If the batteries are stored in temperate climatic zones, they should be charged every three months for 1-2 hours. You should shorten the charging intervals to two months at locations subject to high temperatures.
8. Technical Data 8.1 Electrical specifications INPUT Model No. 1000H(XL) 2000H 2000HXL Phase Single Frequency (46~54)Hz Current(A) 7A 9A 3000H(XL) 12A 16A OUTPUT Model No. 1000H(XL) 2000H(XL) 3000H(XL) Power rating 1kVA/0.7kW 2kVA/1.4kW 3kVA/2.1kW Voltage 220/230/240×(1 士 2%)VAC Frequency 50Hz±0.2Hz (Battery mode) Wave form sinusoidal BATTERIES Model No. 1000H 2000H 3000H Number and type 3×12V 7.2Ah 8×12V 7.2Ah 8×12V 7.2Ah 8.
8. Technical Data 8.4 Dimensions and weights Model No. Dimensions W x D x H (mm) Net Weight (kg) 1000H 145X400X220 14 1000HXL 145X400X220 7 2000H 192X460X340 34.5 2000HXL 192X460X340 15 3000H 192X460X340 35.
9. Introduction – 6000H(XL)/ 10000H(XL) 9.1 Product Specification and Performance 1) General Specification Model 6000H 6000HXL 10000H 10000HXL 6KVA/4.2KW 6KVA/4.2KW 10KVA/7KW 10KVA/7KW 50 50 50 50 Voltage (176-276)VAC (176-276)VAC (176-276)VAC (176-276)VAC Current 31A max. 31A max. 50A max 50A max.
10. Installation 10.1 Unpacking and Inspection 1) Unpack the packaging and check the package contents. The shipping package contains: A UPS A user manual A communication cable A battery cable (for 6000HXL/10000HXL only) 2) Inspect the appearance of the UPS to see if there is any damage during transportation. Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or lacking of some parts. 10.2 Input and output power cords and protective earth ground installation 1.
10. Installation Note: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed. 4) Connect the input and output wires to the corresponding input and output terminals according to the following diagram. Note: you must make sure that the input and output wires and the input and output terminals are connected tightly.
10. Installation Important notes: If the UPS is used in single mode, JPI and JP2 must be connected by 10AWG(6mm2). If the UPS is used in parallel mode, the Jumper between JP1 and JP2 must be removed. 10.3 Operating procedure for connecting the long backup time model UPS with the external battery 1. The nominal DC voltage of external battery pack is 240VDC. Each battery pack consists of 20 pieces of 12V maintenance free batteries in series.
10. Installation 10.4 Parallel operation 1. Brief introduction of the redundancy N+X is currently the most reliable power supply structure. N represents the minimum UPS number that the total load needs; X represents the redundant UPS number, i.e. the fault UPS number that the system can handle simultaneously. The bigger the X is, the higher reliability of the power system is. For occasions where reliability is highly depended on, N+X is the optimal mode.
11. Operation and Operating Mode Operation and maintenance 1) To perform the general operation, follow the stand-alone operating requirement. 2) Startup: The units transfer to INV mode simultaneously as they start up sequentially in utility power mode. Shutdown: the units shut down sequentially in INV mode. When the last one completes the shutdown action, each unit will shut down the inverter simultaneously and transfer to bypass mode. It is easy to operate the equipment, with no previous training.
11. Operation and Operating Mode 2) For long back up time model (“XL” model), please make sure that the battery breaker is in “ON” position. 3) During the course of starting up, the UPS has the same action as if it is connected to utility power except that the utility power LED is not turned on and the battery LED is turned on instead. 3.
11. Operation and Operating Mode 2) New UPS input & output switch should be turned off, according to port sign, link Input & output line and batteries; synchronously, remove the connection between JP1 and JP2. 3) Turn off UPS system, when all UPS work at bypass model, please take apart every UPS repaired board, turn all UPS repaired switches from ‘UPS’ to ‘BPS’ and then turn off all UPS input switch. 4) If UPS system works at single UPS model, then have to remove the connection of JP1 and JP2.
11. Operation and Operating Mode Operational process of removing single UPS: 1) If want to remove UPS which is running normally, please press the close key of the removing one continuously for 2 times 2) Shut off the UPSs own line switch, line output switch outside and battery switch, when this UPS need to remove out. 3) Turn off other UPS which are running, take apart the maintain cover of every UPS and turn all UPS maintain switch from “UPS” to “BPS” until all running UPS turn to BPS mode.
11. Operation and Operating Mode 6. Backup time for the standard model The backup time of the long backup time model is dependent on the external battery pack capacity and the load level as well as other factors. The backup time of standard model may vary from different models and load level.
12. Battery Maintenance This series UPS only requires minimal maintenance. The battery used for standard models are value regulated sealed lead-acid maintenance free battery. These models require minimal repairs. The only requirement is to charge the UPS regularly in order to maximize the expected life of the battery.
13. Notes for Battery Disposal and Battery Replacement 1) Before disposing of batteries, remove conductive jewelry such as necklace, wrist watches and rings. 2) If it is necessary to replace any connection cables, please purchase the original materials from the authorized distributors or service centers, so as to avoid overheat or spark resulting in fire due to insufficient capacity. 3) Do not dispose of batteries or battery packs in a fire, they may explode.
14. Trouble Shooting Problem The #1 Fault LED and the #6 LED are turned on, the buzzer beeps continuously. The #1 Fault LED and the #2 and #5 LED are turned on, and the buzzer beeps continuously. The #1 Fault LED and the #4 LED are turned on, the UPS beeps continuously. The #1 Fault LED and the #5 LED are turned on, the UPS beeps continuously. The utility power LED flashes. The #1 Fault LED and the #2 LED are turned on, the UPS beeps continuously.
15. Operating mode for all models 1. Utility power mode The display panel in utility power mode is shown in the following diagram. The utility power LED and the INV LED are turned on. The load level LEDs will be turned on in accordance with the load capacity connected. 1) If the battery LED is turned on and the utility power LED flashes, it indicates the voltage or frequency of the utility power has exceeded the normal range, the UPS operates in battery mode. Fig 15.
15. Operating mode for all models Fig 15.2 Battery mode diagram 2) When the battery capacity decreases, the number of the battery capacity LEDs turned on will be reduced. If the battery voltage descends to the alarm level, the buzzer will beep once every second to remind the users of insufficient battery capacity and the UPS is soon going to shut down automatically. Then the load operations should be carried out promptly and the loads should be eliminated one by one. 3.
16. Communication Port 16.1 RS232 Interface The following is the pin assignment and description of DB-9 connector. Pin # Description I/O 2 TXD Output 3 RXD Input 5 GND Input 16.2 AS400 Interface(Option) Except for the communication protocol as mentioned above, this series UPS has AS400 card (an optional accessory) for AS400 communication protocol . Please contact your local distributor for details. The following is the pin assignment and description of DB-9 connector in AS400 card.
17. Software for all models Free Software Download – WinPower WinPower is a brand new UPS monitoring software, which provides user-friendly interface to monitor and control your UPS. This unique software provides safely auto shutdown for multi-computer systems while power failure. With this software, users can monitor and control any UPS on the same LAN no matter how far from the UPSs. Installation procedure: 1. Go to the website: http://www.ups-software-download.com/winpower.htm 2.
18. Appendix 1-Display Panel (for 6000H(XL)/10000H(XL)) Power ON/OFF: To turn on the UPS simply by pressing the “ON” button on the front panel continuously for 1 second. Press the “OFF” button on the front panel continuously for 1 second to turn off the UPS. Bypass LED (orange LED): Whenever the bypass LED is turned on, it shows that the loading current is supplied directly from the utility power.
Appendix 2-The Corresponding Form of the LED Display for 6000H(XL)/10000H(XL) No.
Appendix 3-Back Panel The method, type and appearance of the input socket and output socket are vary with different areas, the appearance of the products is based on what it is.
(For XL Model only) Back View of 3000H(XL) Non CE-certified Back View of 3000H(XL) CE-certified Back view of 6000H Back view of 6000HXL 35
Back view of 10000H Back view of 10000HXL 36