Cut Sheet

V8-T7-8 Volume 8—Sensing Solutions CA08100010E—July 2015 www.eaton.com
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
For Customer Service in the U.S. call 1-877-ETN CARE (386-2273),
in Canada call 1-800-268-3578.
For Application Assistance in the U.S. and Canada
call 1-800-426-9184.
7.2
Current and Voltage Sensors
CurrentWatch ECS Series
ECS Series CurrentWatch Current Switches
Contents
Description Page
ECS Series CurrentWatch Current Switches
Standards and Certifications. . . . . . . . . . . . . . . V8-T7-9
Product Selection . . . . . . . . . . . . . . . . . . . . . . . V8-T7-9
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-9
Technical Data and Specifications . . . . . . . . . . V8-T7-10
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-10
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-10
ECS Series CurrentWatch Current Switches
Product Description
The CurrentWatch™ ECS
Series from Eaton’s Electrical
Sector is a family of solid-
state adjustable current
switches, ideal for providing
status information on
electrical equipment. The
ECS is excellent for new
installations, where the
conductors run through the
housing, requiring no cutting.
These switches are also ideal
for retrofits, since split-core
models can be opened to fit
around existing conductors.
The current switch is
accurate, reliable and easy
to install.
The ECS can sense
continuous currents from
1 to 150A and does not
require any supply voltage,
as the power required is
induced from the monitored
conductor. The output is a
non-polarity-sensitive solid-
state contact for switching
AC and DC circuits up to
240 Vac/dc. This switch also
includes an LED indicating
two states: on and below trip
point, and above trip point
with contacts energized. All
ECS Series switches carry an
unconditional five-year
warranty.
Any change in current can be
sensed with the ECS Series.
A change in current may
indicate motor failure, belt
loss/slippage or mechanical
failure. Any of these events
can cause the current to drop
significantly, tripping the
switch and notifying the
controller.
Application Description
Typical Applications
Electronic Proof of
Flow—Current operated
switches eliminate the
need for multiple pipe or
duct penetrations and are
more reliable than electro-
mechanical pressure or
flow switches
Conveyors—Detect jams
and overloads
Lighting Circuits—Easier
to install and more
accurate than photocells
Fans, Pumps and Heating
Elements—Faster
response than temperature
sensors
Critical Motors
Ancillary Equipment
For the most current information
on this product, visit our Web site:
www.eaton.com
Example Application—
Pump Jam and Suction Loss Protection
Features
Universal Outputs—NO
or NC solid-state switch for
control circuits up to 240
Vac/dc, compatible with
most automation systems
Self-Powered—Cuts
installation and operating
costs
Easily Adjustable
Setpoint—Increases
application flexibly and
speeds start-up
Solid- or Split-Core
Housings—Versions
tailored for each type of
installation
LED Indication—Provides
quick visual indication of
contact status
Built-In Mounting Feet—
Simple, two-screw panel
mount or attach with
optional DIN-rail mounting
kit accessory
Jam
AMPS
Overload Setpoint
Current Switch
Motor
Starter
Digital
Input
PLC
B/I Card
Motor
Off
Normal Operation
Time
Motor
Control
Signal