Cut Sheet

V8-T2-34 Volume 8—Sensing Solutions CA08100010E—August 2015 www.eaton.com
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2.3
Limit Switches
LS-Titan Miniature DIN Switches
Technical Data and Specifications
LS-Titan Miniature DIN Switches—IP66, IP67 Complete Units
Note
1
The following applies for LSE-11 and LSE-02: ensure that the power supply operates correctly when setting the operating point.
Units LS, LSM LSE-11/LSE-02 LSE-AI
1
LSE-AU
1
General
Standards IEC/EN 60947 IEC/EN 60947
EN 61000-4
IEC/EN 60947
EN 61000-4
IEC/EN 60947
EN 61000-4
Climatic proofing Damp heat, constant, to IEC
60068-2-78; damp heat,
cyclical, to IEC 60068-2-30
Damp heat, constant, to IEC
60068-2-78; damp heat,
cyclical, to IEC 60068-2-30
Damp heat, constant, to IEC
60068-2-78; damp heat,
cyclical, to IEC 60068-2-30
Damp heat, constant, to IEC
60068-2-78; damp heat,
cyclical, to IEC 60068-2-30
Ambient temperature °F (°C) –13° to 158°F (–25° to 70°C) –13° to 158°F (–25° to 70°C) –13° to 158°F (–25° to 70°C) –13° to 158°F (–25° to 70°C)
Mounting position As required As required As required As required
Protection type IP66, IP67 IP66, IP67 IP66, IP67 IP66, IP67
Terminal capacity of screw
terminal and Cage Clamp
Solid mm
2
1 x (0.5–2.5) 1 x (0.5–2.5) 1 x (0.5–2.5) 1 x (0.5–2.5)
Flexible with ferrules to DIN 46228 mm
2
1 x (0.5–1.5) 1 x (0.5–1.5) 1 x (0.5–1.5) 1 x (0.5–1.5)
Power Supply
Rated voltage U
e
Vdc N/A 12–30 24 (–15%/+20%) 24 (–15%/+20%)
Burden current
12V I
e
mA N/A 15 N/A N/A
24V I
e
mA N/A 18 28–45 24
30V I mA N/A 19 N/A N/A
Contacts/Switching Capacity
Rated impulse withstand voltage U
imp
Vac 4000 N/A N/A N/A
Rated insulation voltage U
i
V 400 N/A N/A N/A
Overvoltage category/
pollution degree
III/3 III/3 N/A N/A
Rated Operational Current
AC–15
24V I
e
A 6 N/A N/A N/A
230V/240V I
e
A 6 N/A N/A N/A
400V/415V I
e
A 4 N/A N/A N/A
DC-13
24V I
e
A3 0.2 N/A N/A
110V I
e
A 0.8 N/A N/A N/A
220V I
e