User`s guide

Monitored ePDU Operation
Eaton
®
User's Guide for Basic, Monitored, and Switched ePDUt S 164202115 Rev 1
9
ePDU Remote Current Meter Setup Guide
Description
The current meter included in this product has both a local LED display and an RJ45
network interface. The local meter display rotates among all of the current channels
and uses a descriptor, “Cn” (where C is the channel number and n is the section
number), to indicate which channel is to be displayed next. The network interface
provides current monitoring capability via a web interface, and email alerts and SNMP
traps can be sent when the unit exceeds customizable thresholds.
Hardware Setup
1. To use the network interface, connect a standard Ethernet cable (included) from
the RJ45 connector labeled NET on the top of the unit to an available port on a
network switch.
2. Connect the power input to an appropriate source.
Configuration and Control via Network Connection
NOTE The unit comes with a default IP address of 192.168.168.168. If you are unable to connect to the
unit via the network connection with this default address, it will be necessary to use a configuration program
from Eaton engineering before using any of the network interfaces. To obtain this program, please contact
technical support at (800) 870-2248.
Default Settings
IP Address: 192.168.168.168
Gateway: 192.168.168.1
Username: Admin
Password: etn
Instructions
1. Using any web browser, navigate to the remote current meter's IP address
(http://192.168.168.168/).
2. A Readings screen will appear that shows all of the available current and
temperature readings for the unit. Click on Refresh to update the screen.
3. To enter configuration mode, click on Configuration on the left-hand side of the
screen. A prompt will appear asking for the username and password; the default
user name is Admin, and the default password is etn.
4. A Configuration screen will appear that shows all of the available options for
the unit, including network settings. After changing any parameters, press the
Update Settings button to save changes, wait about five seconds, then press
the Click Here link to return to the Readings screen.