Outlet-Environmental Status
−− Outlet State Sub Menu −−
1 Outlet Section 1 (18)
2 Outlet Section 2 (916)
3 Outlet Section 3 (1724)
4 Environmental Sensors
−− Other Choices −−
<b> = Back
<s> = Outlet/Environmental status
Select Item Number:
This menu is available from the Main Menu as option 4 and also throughout much of
the interface by pressing the [s] key. The number of sections are listed as they are
present on the Switched ePDU.
Outlet Section
Selecting the option for any outlet section displays an outlet status screen:
−− Outlet Control Sub Menu −−
Outlet Section 1 Measurements
Voltage: 121 V
Current: 0.0 A
Power: 0.0 VA
Outlet Name Current State
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
1 HP Server On
2 PowerEdge Server Off
3 Exchange Server On
4 Disk Array 1 On
5 Switch 1 Off
6 Disk Array 2 On
7 Citrix Server On
8 Backup Server On
−− Other Choices −−
<b> = Back
<s> = Outlet/Environmental status
<n> = Next outlet section
Select Item Number:
The measured voltage, measured current, and calculated apparent power are
displayed at the top of the page. For all single-phase Switched ePDUs (8-outlet,
16-outlet, and some 24-outlet Switched ePDUs), these values correspond to what is
measured for the displayed outlet section. For three-phase Switched ePDUs (most
24-outlet Switched ePDUs), these values are measurements of phase voltage and
phase current and the calculated phase power; values displayed for section 1
correspond to phase X, those for section 2 correspond to phase Y, and those for
section 3 correspond to phase Z. Be sure to read the label next to the measurements
for an exact description.