User`s guide

Switched ePDU Admin Using the Web Interface
Eaton
®
User's Guide for Basic, Monitored, and Switched ePDUt S 164202115 Rev 1
66
Table 16. Unit Status Page
Field Description
Unit Name This field displays the Switched ePDU's name, and in parentheses it also
gives the Switched ePDU's Strapping ID (important when using the
strapping feature because it shows the ID of the Switched ePDU that is
currently being navigated).
Outlets Section Buttons The status for one outlet section at a time is displayed on the page. When
connected to a 16- or 24-outlet Switched ePDU, buttons are present to
switch to each of the additional sections.
Hyperlinked Outlet
Numbers
Each outlet number can be set up with a hyperlink to a URL. Use this field as
a convenient way to store a link to the Web-based configuration for a device
connected to an outlet. The URL for each outlet can be customized in the
Outlet Configuration page (see page 69).
Power Log
Power Log data is collected by multiplying the measured voltage and current to
calculate the apparent power and recording the result at the Power Log Interval
specified on the Unit Configuration page (see page 77). Up to 50 hours (60-minute
time interval), 12 hours 30 minutes (15-minute time interval), or 4 hours 10 minutes
(5-minute time interval) of history may be available at any time. See Figure 16.
NOTE Power Log data is maintained only while the Switched ePDU is in normal operation; all data is lost if
the ePDU is rebooted or the power is disconnected.
Question or Comments about this device? Please contact eaton.com/powerquality for support.
All contents copyright E 2009 Eaton Corporation. All Rights Reserved.
Figure 16. Power Log Page (Typical)