Outlet Configuration
Outlets can be configured in the Outlet Configuration page (see Figure 19). Select the
appropriate Outlets button to display the outlet section to be configured. See Table 19
for field descriptions.
Outlets Section Buttons
Question or Comments about this device? Please contact eaton.com/powerquality for support.
All contents copyright E 2009 Eaton Corporation. All Rights Reserved.
Figure 19. Outlet Configuration Page (Typical)
Table 19. Outlet Configuration Page
Field Description
Name Outlet name (up to 20 characters).
This setting is used to describe the outlet wherever it appears in the
interface.
NOTE If scheduled events or sensors are configured to control an outlet,
changing the outlet name breaks the link and prevents the outlet from being
controlled. Outlet name changes must be manually carried over to
scheduled events and sensor-based outlet control.
Ping Configures the outlet IP address for “watch mode.”
If Ping is enabled and a valid Ping Interval is set in the Network
Configuration page (see page 79), the Switched ePDU pings the IP address
set up for this outlet according to the time specified by the Ping Interval.
If there is no ping response, the outlet reboots. If the ping fails and the outlet
reboots three times in a row, the ping feature for that outlet stops until the
Switched ePDU reboots or the Ping Enabled setting is briefly set to Disabled
and then back to Enabled.
Link (URL) Any hyperlink up to 30 characters.
This feature is designed for ease of accessing all of the devices attached to
one Switched ePDU. After entering a Link, click the outlet number on the
Home page to open a new browser window and navigate to this address.
NOTE Based on the URL entered here, selecting an outlet number from the
Home page opens a new browser window displaying the Web-based
configuration page for the device connected to the outlet.