User`s guide

Switched ePDU Admin Using the Web Interface
Eaton
®
User's Guide for Basic, Monitored, and Switched ePDUt S 164202115 Rev 1
80
Table 27. Network Configuration Settings
Section Field Description
Network Settings
Use DHCP* Select the Use DHCP check box to enable DHCP or clear the check box to disable.
If DHCP is enabled, the IP address, subnet mask, and default gateway values are obtained
from the network DHCP server, and these obtained values overwrite whatever static settings
have been entered.
If DHCP is disabled, the static IP address, subnet mask, and default gateway values entered
below are used to communicate on the network.
Unit IP Address* Enter in standard dot notation (for example, 192.168.168.168).
Subnet Mask* Enter in standard dot notation (for example, 255.255.255.0).
Default Gateway* Enter in standard dot notation (for example, 192.168.168.1).
MAC Address This value is unique to this Switched ePDU and cannot be changed from this page. If
customization is necessary, see “Advanced Boot Configuration” on page 91 for instructions.
Serial Settings
Baud Rate* 9600, 19200, or 38400 baud (default is 9600). All other serial settings are fixed at 8 data bits, no
parity, 1 stop bit, and no flow control.
Data bits Cannot be changed from this page.
Stop bits Cannot be changed from this page.
Flow control Cannot be changed from this page.
Telnet Settings
Enable Access* Select the Telnet Enable Access check box to enable.
Port* Telnet port, any integer from 1 to 65535 (default is 23).
Web Settings
Enable Access* Select the Web Enable Access check box to enable.
Port* Web port, any integer from 1 to 65535 (default is 80).
The Web Port setting only affects Web access when the Enable Secure Web check box is
clear.
Enable Secure Web* Select the Web Enable Secure Web check box to enable.
Each time the Switched ePDU reboots (or power is applied to the Switched ePDU when the
Secure Web is enabled), the boot process takes up to five minutes to generate a new secure
server certificate. During this time the Switched ePDU is unavailable from all interfaces, and
outlet operations, such as power on sequencing, is delayed until the certificate is generated
(the boot process can be monitored over a serial connection).
After the Switched ePDU reboots, the secure Web interface is available at port 443 (this port
number is fixed) using the secure URL format (for example, https://192.168.168.168).
Secure Web Port Fixed port number for the Web interface.
Ping Settings
Enable Ping Select the Enable Ping check box to enable the Switched ePDU to ping the IP address set up
for each outlet (see Outlet Configuration) according to the time specified in the Ping Interval
field. Changes take effect immediately.
If there is no ping response, the outlet reboots. If the ping fails and the outlet reboots three
times in a row, the ping feature for that outlet stops until the Switched ePDU reboots or the
Enable Ping check box is cleared and then reselected.
Ping Interval Any integer from 5 to 60 minutes; changes take effect immediately.
* Requires a soft reboot to take effect (select Soft Reboot from the Unit Configuration page, then click Save Changes).