User Manual

Appendix
12/06 AWB2724-1584GB
104
CAN(open)/easy-NET
Data transmission rate Kbit/s 10, 20, 50, 100, 125, 250, 500
Default: 125
Potential isolation from inputs/outputs/power supply Yes
Bus termination resistor 120 O or EASY-NT-R plug (incl. bus terminating resistor 120 O)
Connection type 2 x RJ45, 8pole
CAN(open) operating mode:
Stations Number max. 126
–PDO type Asynchronous, cyclic, acyclic
Device profile to DS301V4
easy-NET operating mode
Station Number max. 8
Power supply
Rated voltage
Rated value V DC, (%) 24, ( –15, +20)
Permissible range V DC 0.25 to 0.34
Residual ripple % F 5
Input current at 24 V DC, typical mA 140
Voltage dips, IEC/EN 61131-2 ms 10
Power loss at 24 V DC, typical W 3.4
Inputs
Digital inputs
Number 12
Inputs that can be used for analog signals
I 7, 8, 11, 12
Inputs for pulse signals
(High-speed counters)
I 1,2,3,4
Inputs for interrupt generation I 1,2,3,4
Status indication
LCD display
Electrical isolation
From the power supply, PC interface No
Between each other
No
From the outputs, to CAN interfaces Yes
Rated voltage
Rated value V DC 24
On 0 signal
I1 to I6 and I9 to I10 V DC < 5
I7, I8, I11, I12 V DC < 8
On 0 signal
I1 to I6 and I9 to I10 V DC > 15
I7, I8, I11, I12 V DC > 8
Input current on “1” signal (at 24 V DC)
I1 to I6, I9 to I10 mA 3.3
I7, I8, I11, I12 mA 2.2