User Manual

12/06 AWB2724-1584GB
Connecting a pulse
transmitter/incremental
encoder
23
Connecting a pulse transmitter/incremental encoder
Inputs I1 to I4 are designed so that high-speed signals from pulse
transmitters/incremental encoders can be counted.
The following connection options are possible:
2 x pulse transmitters (16-bit)
1 x pulse transmitters (32-bit)
1 x incremental encoder (32-bit).
Connecting pulse transmitter
The figure shows the connection of a pulse transmitter which
sends pulses to input I1. An internal counter processes the pulses.
You can choose between a 16-bit counter (max. 65535) and 32-
bit counter (max. 4294967295). The pulse transmitter for the 32-
bit counter must only be connected to I1. Only if a 16-bit counter
was used at I1, can another pulse transmitter (16-bit) be
connected to I2.
Connecting the incremental value encoder
Figure: 21: Connecting pulse transmitter
0 V
0 V
...V
L01 –
F1
L01 +
I1
I2 I3
I4 I5
I6
L02 +
24 V H
Figure: 22: Connecting the incremental encoder
A,B: square-wave incremental signals that have a 90 degree phase shift
C: Reference signal
K1: Reference window switch
0 V
0 V
...V
L01 –
F1
L01 +
I1
I2 I3
I4 I5
I6
L02 +
AB
24 V H
C
K1