Cut Sheet

Volume 10—Enclosed Control CA08100012E—June 2015 www.eaton.com V10-T2-5
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2.1
NEMA Contactors and Starters
Freedom Full Voltage Controls
C440 Solid-State Overload Modifications
Reliability and Improved Uptime
C440 provides the users
with peace of mind knowing
that their assets are
protected with the highest
level of motor protection
and communication
capability in its class
Extends the life of plant
assets with selectable
motor protection features
such as trip class, phase
unbalance and ground fault
Protects against
unnecessary downtime
by discovering changes in
your system (line/load)
with remote monitoring
capabilities
Status LED provides added
assurance that valuable
assets are protected by
indicating the overload
operational status
Flexibility
Improves return on
investment by reducing
inventory carrying costs
with wide FLA adjustment
(5:1) and selectable trip
class
Design incorporates built-in
ground fault protection
thus eliminating the need
for separate CTs and
modules
Flexible communication
with optional I/O enables
easy integration into plant
management systems for
remote monitoring and
control
Monitoring Capabilities
Individual phase currents
RMS
Average three-phase
current RMS
Thermal memory
Fault indication (overload,
phase loss, phase
unbalance, ground fault)
Safety
IP20 rated terminal blocks
Available in Eaton’s
industry leading
FlashGard MCCs
Tested to the highest
industry standards such as
UL, CSA, CE and IEC
RoHS compliant
For solid-state overload enclosed control, add R63 or R64 modification code after the base Catalog Number.
(Example, ECN0501AAA-R63/B).
Notes
1
Features:
Self-powered
Phase loss protection
Current adjustment knob
±1% repeat accuracy
1NO and 1NC isolated contacts
2
Not UL Listed.
Modification IEC Size NEMA Size
Full Load Current
Adjustment Range (A)
Three-Phase without
Ground Fault Auto/Manual
Reset Overload
Three-Phase with
Ground Fault Auto/Manual
Reset Overload
Selectable Class 10/20/30 Selectable Class 10/20/30
Solid-state electronic overload relay
1
B and C 00 0.33–1.65
2
R63/A R64/A
1–5 R63/B R64/B
4–20 R63/C R64/C
C and D 0 and 1 0.33–1.65
2
R63/A R64/A
1–5 R63/B R64/B
4–20 R63/C R64/C
9–45 R63/D R64/D
D 2 9–45 R63/D R64/D
D, F and G 3 20–100 R63/E R64/E
G 4 28–140 R63/F R64/F
N/A 5 60–300 R63/G R64/G
N/A 6 120–600 R63/H R64/H