Cut Sheet

V10-T17-20 Volume 10—Enclosed Control CA08100012E—November 2012 www.eaton.com
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17.3
Technical Data and Specifications
IEC Contactors and Starters
AC Ratings—AC-1 Operation
AC Ratings—AC-3 Operation
Note
1
At maximum permissible ambient temperature.
Description XTCE007B XTCE009B XTCE012B XTCE015B XTCE018C XTCE025C XTCE032C
Conventional free air thermal current, three-pole, 50–60 Hz
Open
at 40°C (I
th
) 22A 22A 22A 22A 40A 45A 45A
at 50°C (I
th
) 21A 21A 21A 21A 38A 43A 43A
at 55°C (I
th
) 21A 21A 21A 21A 37A 42A 42A
at 60°C (I
th
) 20A 20A 20A 20A 35A 40A 40A
Enclosed 18A 18A 18A 18A 32A 36A 36A
Conventional free air thermal current, single-pole (I
th
)
Open 50A 50A 50A 50A 88A 100A 100A
Enclosed 45A 45A 45A 45A 80A 90A 90A
Description XTCE007B XTCE009B XTCE012B XTCE015B XTCE018C XTCE025C XTCE032C
Rated operational current, 50/60 Hz
1
(I
e
) in amperes
220/230V 7 9 12 15.5 18 25 32
240V 7 9 12 15.5 18 25 32
380/400V 7 9 12 15.5 18 25 32
415V 7 9 12 15.5 18 25 32
440V 7 9 12 15.5 18 25 32
500V 5 7 10 12.5 18 25 32
660/690V 4 5 7 9 12 15 18
1000V — — — — — — —
Rated power (P) in kilowatts
220/230V 2.2 2.5 3.5 4 5 7.5 10
240V 2.2 3 4 4.6 5.5 8.5 11
380/400V 3 4 5.5 7.5 7.5 11 15
415V 4 5.5 7 8 10 14.5 19
440V 4.5 5.5 7.5 8.4 10.5 15.5 20
500V 3.5 4.5 7 7.5 12 17.5 23
660/690V 3.5 4.5 6.5 7 11 14 17
1000V — — — — — — —