Technical Data and Specifications
IEC Contactors and Starters
AC Ratings—AC-4 Operation
Note
1
Example—
The transformer has a nominal current of 10A with an inrush current of 18 times the nominal current. So, the contactor must have an
AC-3 current of 18/6 x 10A = 30A. Using an XTCE032C (32A AC-3) contactor is recommended.
Description XTCE007B XTCE009B XTCE012B XTCE015B XTCE018C XTCE025C XTCE032C
Rated operational current, 50/60 Hz
1
(I
e
) in amperes
220/230V 5 6 7 7 10 13 15
240V 5 6 7 7 10 13 15
380/400V 5 6 7 7 10 13 15
415V 5 6 7 7 10 13 15
440V 5 6 7 7 10 13 15
500V 4.5 5 6 6 1 13 1
660/690V 4 4.5 5 5 8 10 12
1000V — — — — — — —
Rated power (P) in kilowatts
220/230V 1 1.5 2 2 2.5 3.5 4
240V 1.5 1.6 2.2 2.2 3 4 4.5
380/400V 2.2 2.5 3 3 4.5 6 7
415V 2.3 2.8 3.4 3.4 5 6.5 7.5
440V 2.4 3 3.6 3.6 5.5 7 8
500V 2.5 2.8 3.5 3.5 6 8 9
660/690V 2.9 3.6 4.4 4.4 6.5 8.5 10
1000V — — — — — — —