Technical Data and Specifications
IEC Contactors and Starters
AC Ratings—AC-6A Operation
AC Ratings—AC-6B Operation
AC Ratings—AC-1 Operation
Notes
1
Example—
The transformer has a nominal current of 10A with an inrush current of 18 times the nominal current. So, the contactor must have an
AC-3 current of 18/6 x 10A = 30A. Using an XTCE032C (32A AC-3) contactor is recommended.
2
For 225–275A, use 2X 70 mm
2
wire.
3
At maximum permissible ambient temperature.
Description XTCE007B XTCE009B XTCE012B XTCE015B XTCE018C XTCE025C XTCE032C
Transformer loads Values are
application specific
Values are
application specific
Values are
application specific
Values are
application specific
Values are
application specific
Values are
application specific
Values are
application specific
Calculation is I
e
AC-3 = X / 6 * I
e
transformer where X is the inrush current of the transformer and I
e
transformer is the nominal current.
1
Description XTCE007B XTCE009B XTCE012B XTCE015B XTCE018C XTCE025C XTCE032C
Capacitor loads
Individual compensation rated operational current I
e
of three-phase capacitors in amperes
Up to 525V See Volume 5—Motor Control and Protection, CA08100006E, Tab 27 for capacitor ratings
690V See Volume 5—Motor Control and Protection, CA08100006E, Tab 27 for capacitor ratings
Maximum inrush current peak (x I
e
) 30303030303030
Component lifesaving (operations) — — — — — — —
Maximum operating frequency (ops/hr) — — — — — — —
Description XTCE040D XTCE050D XTCE065D XTCE072D XTCE080F XTCE095F XTCE115G XTCE150G XTCE170G
Conventional free air thermal current,
three-pole, 50–60 Hz
Open
at 40°C (I
th
) 60A 80A 98A 98A 110A 130A 160A 190A 275A
2
at 50°C (I
th
) 57A 71A 88A 88A 98A 125A 142A 180A 200A
at 55°C (I
th
) 55A 68A 83A 83A 94A 115A 135A 170A 190A
at 60°C (I
th
) 50A 65A 80A 80A 90A 110A 130A 160A 185A
Enclosed 45A 58A 72A 72A 80A 100A 115A 144A 166A
Conventional free air thermal current,
single-pole (I
th
)
Open 125A 162A 200A 200A 225A 275A 325A 400A 460A
Enclosed 112A 145A 180A 180A 200A 250A 285A 360A 415A