Cut Sheet

Volume 10—Enclosed Control CA08100012E—November 2012 www.eaton.com V10-T17-39
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17.5
Technical Data and Specifications
Lighting Contactors
C30CN Lighting Contactors
Main Power Poles
Maximum AC Voltage and Amp Ratings
Maximum Horsepower Rating
Control Circuit Characteristics
Coil
Control Module
Other Control Module Characteristics
Note
1
8 AWG stranded only.
Auxiliary Contacts Rating
A600, 24 Vdc, 24 VA
Ambient Temperature
–13° to 104°F (–25° to 40°C)
Mounting Position
Vertical three-point mounting only.
Wire Size
Wire Specifications
A202 Lighting Contactors
Terminals
All except 30A devices: Cu/Al
30A devices: Cu only
Ballast load: 600 AC, breaking all lines
Tungsten lamp loads, maximum volts
Line-to-line: 480 Vac
Line-to-neutral: 277 Vac
Load Type
Amps
Continuous
Poles
Single-Phase Three-Phase
Ballast 30 347 Vac 600 Vac
General use 30 600 Vac 600 Vac
Tungsten 20 277 Vac 480 Vac
AC resistive 30 600 Vac 600 Vac
Normal Starting Duty
Volts Horsepower
Single-Pole, Single-Phase
110–120V 1
220–240V 2
Three-Pole, Three-Phase
200–208V 3
220–240V 5
440–480V 10
550–600V 15
Description VA
Inrush 248 VA
Sealed 28 VA
Input
Voltage
Steady State Current at
Rated Voltage (mA)
Maximum
VA
12–24 Vdc 42 2
24 Vac 80 5
115–120 Vac 83 12
200–277 Vac 91 30
Description Specification
Minimum pulse duration (three-wire control module) 250 ms
Maximum allowable leakage current 1.8 mA
EMI 35 V/m
Surge transient peak 6 kV
Frequency range 40–70 Hz
Component
Number
of Cables
Wire Range
(Solid or Stranded)
Wire
Temperature
Power poles 1 14–8 AWG 75°C Cu
2 14–8 AWG
1
75°C Cu
Coil 1 or 2 18–14 AWG 60°/75°C Cu
Control module 1 22–12 AWG 60°/75°C Cu
Auxiliary contacts 1 or 2 22–12 AWG 60°/75°C Cu