Cut Sheet

V10-T17-6 Volume 10—Enclosed Control CA08100012E—November 2012 www.eaton.com
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17.2
Technical Data and Specifications
NEMA Contactors and Starters
Specifications—Sizes 4–8, continued
Note
1
20–30% of rated coil voltage.
Description
Contactor Catalog Number/Size
CN15N
NEMA Size 4
CN15S
NEMA Size 5
CN15T
NEMA Size 6
CN15U
NEMA Size 7
CN15V
NEMA Size 8
AC Magnet Coil Data, continued
Dropout volts—cold 54% 63%
111
Dropout volts—hot 56% 64%
111
Maximum operation rate—ops/hour 2,400 2,400 N/A N/A N/A
Pickup time (ms) 28 25 105 105 70
Dropout time (ms) 14 13 200 200 50
Coil operating range % of rated voltage –15% to +10% –15% to +10% –15% to +10% –15% to +10% –15% to +10%
DC magnet coil data For DC magnet coils (and coil data), see Accessories, Tab 15
Operating temperature –20° to 65°C –20° to 65°C –20° to 65°C –20° to 65°C –20° to 65°C
Maximum operating altitude (ft) 6,000 6,000 6,000 6,000 6,000
Mechanical life 5,000,000 5,000,000 5,000,000 5,000,000 5,000,000
Electrical Life (480V/60 Hz)
AC-3 800,000 500,000 590,000 450,000 420,000
AC-4 70,000 34,000 7,400 5,000 4,200
Wire Range
Power terminals Open—3/0–8 Cu,
Enclosed—
250 kcmil–6 Cu/Al
750 kcmil—2 or
(2) 250 kcmil–3/0 Cu/Al
(2) 750 kcmil–3/0 Cu/Al (3) 750 kcmil– 3/0 Cu/Al (4) 750 kcmil–1/0 Cu/Al
Control terminals 12–16 stranded,
12–14 solid Cu
12–16 stranded,
12–14 solid Cu
12–16 stranded,
12–14 solid Cu
12–16 stranded,
12–14 solid Cu
12–16 stranded,
12–14 solid Cu
Power terminal torque
line and load—lb-in
200 550 550 550 500
Auxiliary contact rating A600, P300 A600, P300 A600, P300 A600, P300 A600, P300