Technical Data and Specifications
Reduced Voltage Starters
Edge and Level Sensing Control
Edge Sensing
Edge sensing requires
+24 Vdc power be
momentarily applied to
Control Terminal Block Pin 1
(with Terminal P at +24 Vdc)
to initiate a start under all
conditions. After a stop or
fault occurs, the +24 Vdc
must be removed, then
reapplied to Terminal Pin 1
before another start can
occur. This control
configuration should be used
when restarting of the motor
after a fault or stop must be
supervised manually or as a
part of a control scheme. The
cycling of +24 Vdc power to
Terminal 1 Pin before starting
is required regardless of the
position of the auto reset
switch on the DIM.
Level Sensing
Level sensing will enable a
motor to restart after a fault
is cleared without cycling
+24 Vdc power to Terminal
Pin 1 as long as:
Terminal Pin P is supplied
with +24 Vdc (to start
from Control Terminal
Block, Terminal Pin 3
must also be enabled)
The auto reset switch on
the DIM is set to enabled
All faults have been reset
This control configuration
should be used where it is
desirable to restart a motor
after a fault without additional
manual or automatic control.
An example of this condition
would be on a remote
pumping station where it is
desirable to automatically
restart a pump after a power
outage without operator
intervention.
Note: If the auto reset feature
is used, CAUTION must be
exercised to ensure that any
restart occurs in a safe manner.