Cut Sheet

Volume 10—Enclosed Control CA08100012E—November 2012 www.eaton.com V10-T17-3
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17.2
Technical Data and Specifications
NEMA Contactors and Starters
Freedom Line
Furnish as indicated Eaton
Class ECN combination
starters manufactured by
Eaton’s electrical sector or
approved equal. All starters
shall be UL listed and
conform to the latest
standards and the National
Electric Code.
Non-Reversing
Reversing
General
All motor starters shall be
NEMA Sizes 0–9. Each
starter shall have one NO
auxiliary contact, or as
scheduled
Overload relays shall be
ambient compensated
bimetallic type with
interchangeable heaters,
calibrated for 1.0 and 1.15
service factor motors.
Electrically isolated NO and
NC contacts shall be
provided on the relay.
Visual trip indication shall
be standard. A test trip
feature shall be provided
for ease of troubleshooting
and shall be conveniently
operable without removing
components or the motor
starter
Control circuit transformers,
where specified, shall be
encapsulated. Primary and
secondary fusing shall be
provided. Unless otherwise
specified, the secondary
shall be 120 Vac. 50 VA is
minimum
Pilot devices, where
specified, shall be oiltight
and mounted in the flange.
Pilot lights shall be
transformer type for longer
lamp life. Pilot device
legend plates shall be
engraved aluminum
Solid-state overloads
(SSOL), when specified,
shall be heaterless and be
capable of selecting Class
10, 20 or 30 protection
with manual or automatic
reset options. Full-load
current settings shall be
dial-adjustable
Enclosure
Enclosures shall be Type 1,
3R, 4, 4X, 7/9 or 12, as
scheduled
The operating mechanism
shall be mounted on the
flange and shall have
positive, non-teasing ON/
OFF action. The handle
shall be color-coded: red for
ON and black for OFF
The operating handle shall
have a means to lock the
handle in the OFF position
with a minimum of three
standard padlocks having
1/4 in diameter shackles
The enclosure sub-panel
shall be easily removed
without disturbing the
operating mechanism on
Sizes 0–3
Enclosures shall have
means for locking the
cover
Short-Circuit Protective Device
Disconnect Switch
Where specified, a
disconnect switch with
double break, rotary blades
and quick make/quick break
action shall be provided
A line shield with test
probe holes for inspection
shall be provided. The
shield shall be removable
The switch shall have
readily visible blades in the
open (OFF) position
The fusible disconnect
switch (through 100A) shall
have built-in fuse pullers to
make it easier to remove
fuses
Circuit Breaker
Where specified, an
adjustable instantaneous
trip, magnetic only circuit
breaker shall be provided
A manual push-to-trip
button shall be provided to
exercise the trip unit
Short-Circuit Rating
Fusible disconnect
switches shall be UL listed
for 100,000 amperes
available when Class R
fuses are used
Combination starters with
adjustable instantaneous
trip, magnetic only circuit
breakers shall be UL listed
for 100,000 amperes
available through 480 Vac
Note specific short-circuit
ratings for the ECP
irrigation pump panel and
the HVAC panel on Page
V10-T17-2
Description Catalog Number
Disconnect switch ECN16
Disconnect switch with control power transformer ECN18
Circuit breaker (HMCPE/HMCP) ECN22
Circuit breaker with control power transformer ECN24
Description Catalog Number
Disconnect switch ECN17
Circuit breaker (HMCPE/HMCP) ECN23