Cut Sheet

V10-T17-14 Volume 10—Enclosed Control CA08100012E—November 2012 www.eaton.com
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17.3
Technical Data and Specifications
IEC Contactors and Starters
Frame F–G
Coil Data—Frame F–G
Note
1
At 24V: 0.7–1.3 without additional auxiliary contact modules and ambient temperature +40°C (104°F).
XTCE80F XTCE95F XTCE115G XTCE150G
Voltage Tolera nce
Pickup (x U
c
)
AC operated 0.8–1.1 0.8–1.1 0.8–1.1 0.8–1.1
DC operated 0.7–1.2
1
0.7–1.2
1
0.7–1.2
1
0.7–1.2
1
Dropout (x U
c
)
AC operated 0.3–0.6 0.3–0.6 0.25–0.6 0.25–0.6
DC operated 0.15–0.6 0.15–0.6 0.15–0.6 0.15–0.6
Power Consumption of the Coil at Cold State and 1.0 x U
c
AC operated
Single-voltage coil 50 Hz
Pickup VA 310 310 180 180
Pickup W 165 165 130 130
Sealing VA 26 26 3.1 3.1
Sealing W 5.8 5.8 2.1 2.1
Single-voltage coil 60 Hz
Pickup VA 345 345 170 170
Pickup W 190 190 130 130
Sealing VA 30 30 3.1 3.1
Sealing W 7.1 7.1 2.1 2.1
50/60 Hz
Pickup VA 372 328 170 170
Pickup W 190 190 130 130
Sealing VA 37.1 22.6 3.1 3.1
Sealing W 7.5 6.1 2.1 2.1
DC operated
Pickup W 90 at 24V 90 at 24V 149 at 24V 149 at 24V
Sealing W 1.3 at 24V 1.3 at 24V 2.1 at 24V 2.1 at 24V
Duty factor (%DF) 100 100 100 100
Switching Time at 100% U
c
(Approximate Values)
Main contact
AC operated
Closing delay (ms) <20 <20 <33 <33
Opening delay (ms) <14 <14 <41 <41
DC operated
Closing delay (ms) <45 <45 <35 <35
Opening delay (ms) <34 <34 <30 <30
Arcing time (ms) 15 15 15 15
Permissible residual current with actuation of
A1–A2 by the electronics (with 0 signal) (mA)
<
1
<
1
<
1
<
1
Electromagnetic Compatibility (EMC)
Emitted interference To EN60947-1
Noise immunity To EN60947-1